(G) Control parameters
Parameters
5 - 542
5.13.5
Adjustable 5 points V/F
By setting a desired V/F characteristic from the start up to the base frequency or base voltage with the
V/F control (frequency voltage/frequency), a dedicated V/F pattern can be generated.
Optimal V/F pattern matching the torque characteristics of the facility can be set.
●
By setting the V/F1 (first frequency voltage/first frequency) to V/F5 parameters in advance, a
desired V/F characteristic can be obtained.
●
For an example, with the equipment with large static friction factor and small dynamic friction
factor, large torque is required only at the start up, so a V/F pattern that will raise the voltage only
at the low-speed range is set.
Pr.
Name
Initial
value
Setting range
Description
71
C100
Applied motor
0
2
Standard motor (such as SF-JR)
Adjustable 5 points V/F
Others
Refer to page 5-297.
100
G040
V/F1(first frequency)
9999
0 to 590 Hz,
9999
Set each point of the V/F pattern
(frequency, voltage).
9999: Do not set V/F
101
G041
V/F1(first frequency voltage)
0 V
0 to 1000 V
102
G042
V/F2(second frequency)
9999
0 to 590 Hz,
9999
103
G043
V/F2(second frequency voltage)
0 V
0 to 1000 V
104
G044
V/F3(third frequency)
9999
0 to 590 Hz,
9999
105
G045
V/F3(third frequency voltage)
0 V
0 to 1000 V
106
G046
V/F4(fourth frequency)
9999
0 to 590 Hz,
9999
107
G047
V/F4(fourth frequency voltage)
0 V
0 to 1000 V
108
G048
V/F5(fifth frequency)
9999
0 to 590 Hz,
9999
109
G049
V/F5(fifth frequency voltage)
0 V
0 to 1000 V
I002752E
Fig. 5-263:
V/F characteristic
V/F
V/F
V/F
0
V/F5
V/F4
V/F3
V/F2
V/F1
Voltage
Frequency
Base
frequency
Pr. 3
Torque
boost
Pr. 0
Base
frequency
voltage
Pr. 19
V/F Characteristic
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......