Parameters
5 - 528
Ethernet IP address for command source selection (Pr. 1449 to Pr. 1454)
●
To limit the network devices that send the operation or speed command through the Ethernet
network (Modbus®/TCP or CC-Link IE Field Network Basic), set the range of IP addresses of the
devices.
●
When Pr. 1449 to Pr. 1452 = "0 (initial value)", no IP address is specified for sending commands
through the Ethernet network. In this case, operation through the Ethernet network (Modbus®/
TCP or CC-Link IE Field Network Basic) is not available.
●
When four or more clients attempt a connection to the inverter during Modbus®/TCP communi-
cation, the connection attempted from outside of the IP address range set for Ethernet command
source selection may be forced to be closed.
●
The setting range for command source selection depends on the settings in Pr. 1451 and Pr. 1453,
and Pr. 1452 and Pr. 1454. (Either of the settings can be larger than the other in Pr. 1451 and
Pr. 1453, and Pr. 1452 and Pr. 1454.)
●
When "9999 (initial value)" is set in Pr. 1453 and Pr. 1454, the range is invalid.
Example
Setting example 1:
In this case, the IP address range for command source selection via Ethernet communication is
"192.168.x (1 to 3).xxx (100 to 150)".
I003112A
Fig. 5-253:
Ethernet IP address for command source selection setting example 1
Example
Setting example 2:
In this case, the IP address range for command source selection via Ethernet communication is
"192.168.2.xxx (50 to 100)".
I003113A
Fig. 5-254:
Ethernet IP address for command source selection setting example 2
192
168
1
100
ʊ
ʊ
3
150
Pr. 1449
Ethernet IP address for
command source selection
The range is between the
values set in both
parameters.
Pr. 1450
Pr. 1451
Pr. 1452
Pr. 1453
Pr. 1454
Command source selection
range setting for the
Ethernet IP address
The range is between
the values set in both
parameters.
192
168
2
100
ʊ
ʊ
9999
50
Pr. 1449
Ethernet IP address for
command source selection
Pr. 1450
Pr. 1451
Pr. 1452
Pr. 1453
Pr. 1454
Command source selection
range setting for the
Ethernet IP address
The range is between
the values set in both
parameters.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......