Parameters
(A) Application parameters
FR-F800
5 - 391
Setting multiple PID pre-charge functions
●
When the second pre-charge function is set, two sets of pre-charge functions can be switched for
use. The second pre-charge function is enabled by turning ON the RT signal.
●
The second pre-charge function parameters and signals function in the same way as the following
parameters and signals of the first pre-charge function. Refer to the first pre-charge function when
setting the second pre-charge functions.
Classification
First pre-charge function parameters
Second pre-charge function parameters
Pr.
Name
Pr.
Name
Parameter
760
Pre-charge fault selection
765
Second pre-charge fault selection
761
Pre-charge ending level
766
Second pre-charge ending level
762
Pre-charge ending time
767
Second pre-charge ending time
763
Pre-charge upper detection level
768
Second pre-charge upper detection
level
764
Pre-charge time limit
769
Second pre-charge time limit
1132
Pre-charge change increment amount
1133
Second pre-charge change increment
amount
Tab. 5-191:
Parameters for setting multiple PID pre-charge functions
Classification
First pre-charge function parameters
Second pre-charge function parameters
Signal
Name
Signal
Name
Input signal
X77
Pre-charge end command
X78
Second pre-charge end command
Output signal
Y49
During pre-charge operation
Y50
During second pre-charge operation
Y51
Pre-charge time over
Y52
Second pre-charge time over
Y53
Pre-charge level over
Y54
Second pre-charge level over
Tab. 5-192:
I/O signals for multiple PID pre-charge functions
NOTES
The second PID pre-charge function is valid also when the first pre-charge function is set to invalid
and the second pre-charge function is set.
When "10" (second function enabled only during constant-speed operation) is set to Pr. 155, the
second PID function is not selected even if the RT signal turns ON.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......