(T) Multi-Function Input Terminal Parameters
Parameters
5 - 280
5.9.7
Checking of current input on analog input terminal
When current is input to the analog input terminal 2 and terminal 4, operation when the current input
has gone below the specified level (loss of analog current input) can be selected. It is possible to con-
tinue the operation even when the analog current input is lost.
Analog current input loss condition (Pr. 778)
●
When the condition of current input to the terminal 4 (terminal 2) continues to be 2 mA or less
for Pr. 778 setting time, it is considered as loss of analog current input and alarm (LF) signal is
turned ON. The LF signal will turn OFF when the current input becomes 3 mA or higher.
●
For the LF signal, set "98 (positive logic) or 198 (negative logic)" in any of Pr. 190 to Pr. 196 "output
terminal function selection" to assign the function.
Pr.
Name
Initial value
Setting range
Description
573
T052
4 mA input check selection
9999
1
Continues the operation with output
frequency before the current input loss.
2
4 mA input fault is activated when the
current input loss is detected.
3
Decelerates to stop when the current
input loss is detected. After it is stopped,
4 mA input fault (E.LCI) is activated.
4
Continues operation with the Pr. 777
setting.
9999
No current input check
777
T053
4 mA input check operation
frequency
9999
0 to 590 Hz
Set the running frequency for current
input loss. (Valid when Pr. 573 = "4")
9999
No current input check when Pr. 573 = "4"
778
T054
4 mA input check filter
0 s
0 to 10 s
Set the current input loss detection time.
Fig. 5-127:
4mA input check of current input
I001196E
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
When the Pr. 573
≠
"9999" and terminal 4 (terminal 2)
is calibrated to 2 mA or less with C2 (Pr. 902)
(C5 (Pr. 904)), analog input frequency that is 2 mA or
less will become input current loss, thus it will not be
as the bias setting frequency.
60 Hz
2 mA
4 mA
20 mA
Normal use range
Analog
input
Current input
decrease detection
When C3 (C6) = 0 %
Set frequency
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......