Precautions for use of the inverter
Countermeasures against deterioration of the 400 V class motor insulation
FR-F800
3 - 19
3.5
Countermeasures against deterioration of the 400 V class
motor insulation
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor
terminals. Especially in a 400 V class motor, the surge voltage may deteriorate the insulation. When
the 400 V class motor is driven by the inverter, consider the following countermeasures:
Countermeasures (With induction motor)
It is recommended to take one of the following countermeasures:
●
Rectifying the motor insulation and limiting the PWM carrier frequency according to the wiring
length
For the 400 V class motor, use an
insulation-enhanced motor.
Specifically:
–
Order a "400 V class inverter-driven insulation-enhanced motor".
–
For the dedicated motor such as the constant-torque motor and low-vibration motor, use an
"inverter-driven dedicated motor".
–
Set Pr. 72 "PWM frequency selection" as indicated below according to the wiring length.
●
Suppressing the surge voltage on the inverter side
–
For the FR-F840-01160(55K) or lower, connect the surge voltage suppression filter (FR-ASF-H/
FR-BMF-H) to the output side.
–
For the FR-F840-01800(75K) or higher, connect the sine wave filter (MT-BSL/BSC) to the output
side.
Countermeasures (With PM motor)
When the wiring length exceeds 50 m, set "9" (6 kHz) or less in Pr. 72 "PWM frequency selection".
Wiring length
50 m or shorter
50 m to 100 m
Longer than 100 m
Pr. 72 "PWM frequency selection"
15 (14.5 kHz)
9 (9 kHz)
4 (4 kHz)
Tab. 3-14:
Setting of Pr. 72 according to the wiring length
NOTES
For the details of Pr. 72 "PWM frequency selection", refer to page 5-88. (When using an optional
sine wave filter (MT-BSL/BSC), set "25" (2.5 kHz) in Pr. 72.)
For the details of the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) and the sine wave filter
(MT-BSL/BSC), refer to the Instruction Manual of each option.
A surge voltage suppression filter (FR-ASF-H/FR-BMF-H) can be used under V/F control and
Advanced magnetic flux vector control.
A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under differ-
ent control modes.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......