Installation and wiring
Control circuit
FR-F800
2 - 61
Safety stop function operation
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and
SD to use the inverter. (In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are
respectively shorted with shorting wires.)
If any of the protective functions shown in the following table is activated, the terminal SO turns
OFF.
If the internal safety circuit is operated normally, the terminal SO remains ON until E.SAF is
displayed, and the terminal SO turns OFF when E.SAF is displayed.
"
SA is displayed when the terminals S1 and S2 are identified as OFF due to the internal safety circuit
failure.
!
If another fault occurs at the same time as E.SAF, the other fault can be displayed.
If another warning occurs at the same time as SA, the other warning can be displayed.
For more details, refer to the Safety stop function instruction manual (BCN-A23228-001).
(Find a PDF copy of this manual in the CD-ROM enclosed with the product.
Input
power
Internal
safety circuit
status
Input terminal
,
Output
terminal
Inverter
running status
Operation panel indication
S1
S2
SO
E.SAF
!
SA
OFF
⎯
⎯
⎯
OFF
Output shutoff
(Safe state)
Not displayed
Not displayed
ON
Normal
ON
ON
ON
Drive enabled
Not displayed
Not displayed
Normal
ON
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
ON
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
OFF
ON
Output shutoff
(Safe state)
Not displayed
Displayed
Fault
ON
ON
OFF
Output shutoff
(Safe state)
Displayed
Not displayed
"
Fault
ON
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
ON
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Tab. 2-27:
Description of Safety stop function operation
Fault record
Operation panel
indication
Fault record
Operation panel
indication
Option fault
E.OPT
24 V DC power fault
E.P24
Communication option fault
E.OP1
Safety circuit fault
E.SAF
Parameter storage device fault
E.PE
Overspeed occurrence
E.OS
Retry count excess
E.RET
CPU fault
E.CPU
Parameter storage device fault
E.PE2
E.5 to E.7
Operation panel power supply
short circuit/
RS-485 terminal power supply
short circuit
E.CTE
Internal circuit fault
E.13
Tab. 2-28:
Indication of internal safety circuit failures
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......