(H) Protective function parameter
Parameters
5 - 154
Overheat protection to match the characteristic of the motor
(Pr. 600 to Pr. 604, Pr. 692 to Pr. 696)
●
The activation level of the electronic thermal O/L relay can be varied to match the motor
temperature characteristic.
●
The electronic thermal O/L relay's activation level can be set using the combination of three points
(Pr. 600, Pr. 601), (Pr. 602, Pr. 603), (Pr. 604, Pr. 9). Two or more points are required for setting.
●
The electronic thermal O/L relay's activation level can be set to using the combination of three
points (Pr. 692, Pr. 693), (Pr. 694, Pr. 695), (Pr. 696, Pr. 51) when the RT signal is ON.
●
When setting Pr. 600, Pr. 602, Pr. 604 (Pr. 692, Pr. 694, Pr. 696) to the same frequency, the following
graph's upper level will be applied.
Fig. 5-54:
Overheat protection setting
I002586E
I002833E
Fig. 5-55:
Setting examples
Fig. 5-56:
Overheat protection setting example
I002587E
NOTE
Make sure to set the parameters according to the motor temperature characteristic used.
Parameters referred to
Pr. 71
Applied motor
=>
Pr. 72
PWM frequency selection
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Pr. 190 to Pr. 196
(output terminal function selection)
=>
100%
Continuous operation characteristic
Load ratio (ratio to Pr. 9 (Pr. 51)) [%]
Output
frequency
Pr. 603
(Pr. 695)
Pr. 601
(Pr. 693)
Pr. 600
(Pr. 692)
Pr. 602
(Pr. 694)
Pr. 604
(Pr. 696)
Load ratio
Load ratio
Frequency
Setting
example 1
Setting
example 2
Pr. 9 = 100% of the rated
motor current
Pr. 600 = 6 Hz
Pr. 601 = 50 %
Pr. 602 = 30 Hz
Pr. 603 = 70 %
Pr. 604 = 60 Hz
Pr. 600 = 120 Hz
Pr. 601 = 800 %
Pr. 602 = 3 Hz
Pr. 603 = 50 %
Frequency [
Pr. 604 = 80 Hz
120 Hz
60 Hz
3 Hz
50 %
60 %
100 %
6 Hz
30 Hz
60 Hz
100 %
70 %
50 %
100
80
50
10
Load ratio [%]
Output frequency [Hz]
Pr. 600 = 10 Hz
Pr. 601 = 80 %
Pr. 602 = 10 Hz
Pr. 603 = 50 %
Pr. 604 = 10 Hz
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......