background image

4

3 WIRING

CAUTION

To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.

After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.

Set the voltage/current input switch in the correct position. An incorrect setting may cause a fault, failure or malfunction.

MCCB

R/L1

S/L2
T/L3

R1/L11

S1/L21

PC

10E

(+10V)

10

(+5V)

2

3

1

1

4

C1

B1

A1

U

V

W

AM

5

*1

MC

C2

B2

A2

AU

PTC

TXD+

TXD-

RXD+

RXD-

SG

SINK

SOURCE

*3

STF

STR

STOP

RH

RM

RL

JOG

RT

MRS

RES

AU

CS

SD

RUN

SU

IPF

OL

FU

SE

ON

OFF

VCC

(+)

(-)

2

*4

5

(+)

(-)

*4

GND

*4

(-)

(+)

PR

*7

PX

*7

*5

5V

*2

ON

4 2

OFF

*4

CN8

*6

24V

N/-

P/+

P1

(-)

(+)

CA

     

Source logic

Main circuit terminal

Control circuit terminal

Jumper

Jumper

Jumper

*1.DC reactor 

Remove the jumper across P1 
and P/+ for the 01160 or less if a 
DC reactor is connected. Be sure 
to connect the DC reactor sup-
plied with the 01800 or more. 

Earth

*6.The CN8 connector (for 

MT-BU) is provided with the
01800 or more

Earth

Motor

*2.To supply power to the control circuit 

separately, remove the jumper 
across R1/L11 and S1/L21.

3-phase AC

power supply

Connector for
with/without internal
EMC filter

Main circuit

Control circuit

Terminal functions
vary with the input
terminal assignment. 
(Pr. 178 to Pr. 189)

Control input signals (No voltage input allowed)

Forward rotation

start

Reverse rotation

start

Start self-holding selection

High speed

Middle speed

Low speed

Multi-speed selection

Jog operation

Second function selection

Output stop

Reset

Terminal 4 input selection

(Current input selection)

Selection of automatic restart after

instantaneous power failure

Contact input common (Sink*)

*3. AU terminal can be 

used as PTC input
terminal.

24VDC power supply/max. 100mA load current

Contact input common(Source*)

*(Common for external power supply transistor)

Frequency setting signal (Analog)

Auxiliary

input

Terminal 4

input

(Current

input)

0 to 5VDC

0 to ±10VDC

4 to 20mADC

0 to 10VDC
4 to 20mADC

0 to ±5VDC

0 to 5VDC
0 to 10VDC

PU 
connector

Connector for 
plug-in option 
connection

Option connector 1

Terminating

resistor

*4.Terminal input specifications 

can be changed by analog 
input specifications switchover 
(Pr. 73, Pr. 267) (initial settings 
in frame). Set the voltage/cur-
rent input switch in the OFF 
position to select voltage input 
(0 to 5V/0 to 10V) and ON to 
select current input (0 to 
20mA). Terminal 2 and 10 can 
be used as PTC input terminal. 
(Pr. 561). 

*5.It is recommended to use 2W, 

1k

Ω

 when the frequency set-

ting signal is changed fre-
quently.

Relay output 1
(Alarm output)

Relay output 2

Running

Instantaneous
power failure

Up to frequency

Overload

Terminal functions
vary with the output
terminal assignment.
(Pr. 195, Pr. 196)

Terminal functions
vary with the output
terminal assignment.
(Pr. 190 to Pr. 194)

Frequency detection

Open collector output common
Sink/source common

Analog current output
(0 to 20mADC)

Analog signal output
(0 to 10VDC)

RS-485 terminal

s

Data transmission

Data reception

(Permissible load
current 100mA)

Frequency setting

potentiometer

1/2W, 1k

Ω

M

3~

Earth

Inrush current 

limit circuit

*7 Do not use PR and PX terminals. 

Please do not remove the jumper con-
nected to terminal PR and PX.

Brake resistor 
(Option)

Brake unit 
(Option)

Open collector output

Relay output

Voltage/current 
input switch

Option connector 2

Analog common

Summary of Contents for FR-F740-00023-EC

Page 1: ...RAMETER 14 TROUBLESHOOTING 21 APPENDIX 24 Thank you for choosing this Mitsubishi Inverter Please read through this Installation guideline and the enclosed CD ROM to operate this inverter correctly Do not use this product until you have a full knowledge of the equipment the safety information and the instructions Please forward this Installation guideline and the CD ROM to the end user 1 2 3 4 5 6 ...

Page 2: ... E 2 E 5 E PID E PCH E LCI 앫Resetting the inverter Additions 앫Breaker selection when using the inverter as UL or cUL listed product 앫Electronic thermal relay function operation characteristic Partial modification 앫Appendix 1 Instructions for compliance with the EU Directives For Maximum Safety 앫 Mitsubishi transistorized inverters are not designed or manufactured to be used in equipment or systems...

Page 3: ...is involved in the wiring or inspection of this equipment should be fully competent to do the work 앫 Always install the inverter before wiring Otherwise you may get an electric shock or be injured 앫 If your application requires by installation standards an RCD residual current device as up stream protection please select according to DIN VDE 0100 530 as following Single phase inverter type A or B ...

Page 4: ...ent as it will restart suddenly after an alarm stop 앫 Since pressing the key may not stop output depending on the function setting status provide a circuit and switch separately to make an emergency stop power off mechanical brake operation for emergency stop etc 앫 Make sure that the start signal is off before resetting the inverter alarm A failure to do so may restart the motor suddenly 앫 The inv...

Page 5: ...uency inverter is not designed to continuously hold a load Use an electro mechanical holding brake on the motor for this purpose 앫 Before running an inverter which had been stored for a long period always perform inspection and test operation 앫 For prevention of damage due to static electricity touch nearby metal before touching this product to eliminate static electricity from your body 앫 Provide...

Page 6: ......

Page 7: ...nverter type Serial number Inverter type Input rating Output rating Serial number Overload current rating Ambient temperature LD 120 60s 150 3s 50 C SLD 110 60s 120 3s 40 C Symbol Voltage Class F746 Three phase 400V class waterproof structure IP54 standard IEC 60529 2001 specification Symbol Type number 00023 to 01160 Displays the rated current Production year month 00023 to 00620 00770 to 12120 F...

Page 8: ...freezing for selected overload capability 150 Pr 570 0 10 C to 40 C 30 C for FR F746 non freezing for selected overload capability 120 Pr 570 1 Enclosure Ambient humidity 90 RH or less non condensing Storage temperature 20 C to 65 C Atmosphere Indoors No corrosive and flammable gases oil mist dust and dirt Altitude Maximum 1000 m above sea level Vibration 5 9m s2 햲 or less at 10 to 55 Hz direction...

Page 9: ...12 FR F740 02160 02600 EC 465 400 620 595 300 12 FR F740 03250 03610 EC 465 400 740 715 360 12 FR F740 04320 04810 EC 498 400 200 1010 985 380 12 FR F740 05470 06830 EC 680 600 300 1010 985 380 12 FR F740 07700 08660 EC 790 630 315 1330 1300 440 12 FR F740 09620 12120 EC 995 900 300 1580 1550 440 12 FR F746 FR F746 00023 00126 EC 249 180 395 380 210 7 FR F746 00170 00250 EC 319 255 395 380 240 7 F...

Page 10: ...nction selection Output stop Reset Terminal 4 input selection Current input selection Selection of automatic restart after instantaneous power failure Contact input common Sink 3 AU terminal can be used as PTC input terminal 24VDC power supply max 100mA load current Contact input common Source Common for external power supply transistor Frequency setting signal Analog Auxiliary input Terminal 4 in...

Page 11: ...ew size M4 Motor Screw size M4 M 3 L1 L2 L3 Jumper Charge lamp Screw size M5 Screw size M5 Power supply Motor Jumper Screw size M4 M 3 L1 L2 L3 Jumper Jumper Charge lamp Screw size M4 Screw size M6 Power supply Motor Screw size M6 M 3 L1 L2 L3 Screw size M4 Charge lamp Jumper Screw size 00770 M6 00930A 01160A M8 Jumper Power supply Screw size 00770 M6 00930 01160 M8 Motor M 3 L1 L2 L3 Screw size M...

Page 12: ... from the motor shaft 앫 When wiring the inverter main circuit conductor of the 05470 or more tighten a nut from the right side of the conductor When wiring two wires place wires on both sides of the conductor refer to the drawing For wiring use bolts nuts provided with the inverter Jumper Charge lamp Screw size M10 Power supply Motor Screw size M4 M 3 L1 L2 L3 DC reactor Screw size M12 for Option ...

Page 13: ...46 00250 EC M4 1 5 5 5 4 5 5 4 FR F740 746 00310 EC M5 2 5 8 5 8 5 FR F740 746 00380 EC M5 2 5 14 5 8 5 FR F740 746 00470 EC M6 4 4 14 6 14 6 FR F740 746 00620 EC M6 4 4 22 6 22 6 FR F740 746 00770 EC M6 4 4 22 6 22 6 FR F740 746 00930 EC M8 7 8 38 8 38 8 FR F740 746 01160 EC M8 7 8 60 8 60 8 FR F740 01800 EC M8 M10 7 8 60 8 60 8 FR F740 02160 EC M10 14 7 100 10 100 10 FR F740 02600 EC M10 14 7 10...

Page 14: ...ed cable with continuous maximum permissible temperature of 75 C Assumes that the ambient temperature is 50 C or less and the wiring distance is 20m or less For the 01800 or more the recommended cable size is that of the LMFC cable heat resistant flexible cross linked polyethylene insulated cable with continuous maximum permissible temperature of 90 C Assumes that the ambient temperature is 50 C o...

Page 15: ...frequency inverter output voltage dV dT If the motor requires a rise speed of 500 V μs or less you must install a filter in the output of the inverter Please contact your Mitsubishi dealer for more details 3 2 3 Cable size of the control circuit power supply terminal R1 L11 S1 L21 앫 Terminal screw size M4 앫 Cable size 0 75mm2 to 2mm2 앫 Tightening torque 1 5N m Pr 72 PWM frequency selection setting...

Page 16: ... the contact input terminals e g STF of the control circuit 앫 Always apply a voltage to the alarm output terminals A B C via a relay coil lamp etc 앫 It is recommended to use the cables of 0 75mm2 gauge for connection to the control circuit terminals If the cable gauge used is 1 25mm2 or more the front cover may be lifted when there are many cables running or the cables are run improperly resulting...

Page 17: ...installed immediately remove it 앫 Before starting wiring or other work after the inverter is operated wait for at least 10 minutes after the power supply has been switched off and check that there are no residual voltage using a tester or the like The capacitor is charged with high voltage for some time after power off and it is dangerous 앫 A short circuit or earth fault on the inverter output sid...

Page 18: ...and such will activate When MC is provided for switching to the commercial power supply for example switch it ON OFF after the inverter and motor have stopped 앫 Instructions for overload operation When performing operation of frequent start stop of the inverter increase decrease in the temperature of the transistor element of the inverter may repeat due to a continuous flow of large current shorte...

Page 19: ...he motor current and consider the backup system such as checking up as below according to the level of importance of the system Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector Note that the motor current runs as the motor is ru...

Page 20: ... 5s 12 DC injection brake operation voltage 0 to 30 4 2 1 4 13 Starting frequency 0 to 60Hz 0 5Hz 14 Load pattern selection 0 1 1 15 Jog frequency 0 to 400Hz 5Hz 16 Jog acceleration deceleration time 0 to 3600 360s 0 5s 17 MRS input selection 0 2 0 18 High speed maximum frequency 120 to 400Hz 120 60Hz 1 19 Base frequency voltage 0 to 1000V 8888 9999 8888 20 Acceleration deceleration reference freq...

Page 21: ... Range Initial Value 67 Number of retries at alarm occurrence 0 1 to 10 101 to 110 0 68 Retry waiting time 0 to 10s 1s 69 Retry count display erase 0 0 70 Special regenerative brake duty 3 0 to 10 0 71 Applied motor 0 1 2 20 0 72 PWM frequency selection 0 to 15 0 to 6 25 1 2 73 Analog input selection 0 to 7 10 to 17 1 74 Input filter time constant 0 to 8 1 75 Reset selection disconnected PU detect...

Page 22: ...ation stopping time 0 to 360s 0 5s Parameter Name Setting Range Initial Value 142 Backlash deceleration stopping frequency 0 to 400Hz 1Hz 143 Backlash deceleration stopping time 0 to 360s 0 5s 144 Speed setting switchover 0 2 4 6 8 10 102 104 106 108 110 4 145 PU display language selection 0 to 7 1 147 Acceleration deceleration time switching frequency 0 to 400Hz 9999 9999 148 Stall prevention lev...

Page 23: ...l function selection 2 193 OL terminal function selection 3 194 FU terminal function selection 4 Parameter Name Setting Range Initial Value 195 ABC1 terminal function selection 0 to 5 7 8 10 to 19 25 26 45 to 54 64 67 70 to 79 82 85 90 91 94 to 96 98 99 100 to 105 107 108 110 to 116 125 126 145 to 154 164 167 170 179 182 185 190 191 194 to 196 198 199 9999 1 99 196 ABC2 terminal function selection...

Page 24: ...415 Inverter operation lock mode setting 0 1 0 495 Remote output selection 0 1 10 11 0 496 Remote output data 1 0 to 4095 0 497 Remote output data 2 0 to 4095 0 498 PLC function flash memory clear 0 to 9999 0 502 Stop mode selection at communication error 0 to 3 0 503 Maintenance timer 0 1 to 9998 0 504 Maintenance timer alarm output set time 0 to 9998 9999 9999 505 Speed setting reference 1 to 12...

Page 25: ...tial Value 753 Second PID action selection 10 11 20 21 40 41 50 51 60 61 70 71 80 81 90 91 100 101 110 111 120 121 140 141 9999 9999 754 Second PID control automatic switchover frequency 0 to 400Hz 9999 9999 755 Second PID action set point 0 to 100 9999 9999 756 Second PID proportional band 0 1 to 1000 9999 100 757 Second PID integral time 0 1 to 3600s 9999 1 s 758 Second PID differential time 0 0...

Page 26: ... C5 904 2 Terminal 4 frequency setting bias frequency 0 to 400Hz 0Hz Parameter Name Setting Range Initial Value C6 904 2 Terminal 4 frequency setting bias 0 to 300 20 126 905 2 Terminal 4 frequency setting gain frequency 0 to 400Hz 50Hz C7 905 2 Terminal 4 frequency setting gain 0 to 300 100 C8 930 2 Current output bias signal 0 to 100 0 C9 930 2 Current output bias current 0 to 100 0 C10 931 2 Cu...

Page 27: ...atic restart or the execution of a reset 앫 If protective functions were activated i e the inverter switched off with an error message follow the instructions for error correction provided in the manual for the inverter Especially in the case of short circuits or earth contacts in the inverter output and mains overvoltages the cause of the fault must be determined prior to switching on again as a r...

Page 28: ...nly be performed when a fault occurs 앫 Switch OFF the power once then switch it ON again after the indicator of the operation panel turns OFF 앫 Turn ON the reset signal RES for more than 0 1 s If the RES signal is kept ON Err appears flickers to indicate that the inverter is in a reset status NOTE When a fault occurs during PLC function turning ON of X51 signal can release fault without interrupti...

Page 29: ...ay function 49 H31 E FIN Fin overheat 64 H40 E IPF Instantaneous power failure protection 80 H50 E BE Brake transistor alarm detection Internal circuit error 112 H70 to to Fault E UVT Undervoltage protection 81 H51 E ILF Input phase failure 82 H52 E OLT Stall prevention 96 H60 E GF Output side earth ground fault overcurrent protection 128 H80 E LF Output phase failure protection 129 H81 E OHT Exte...

Page 30: ...ures and ensure the conformity of the inverter used in the residential area NOTES 앫 First environment Environment including residential buildings Includes buildings directly connected without a transformer to the low voltage power supply network which supplies power to residential buildings 앫 Second environment Environment including all buildings except buildings directly connected without a trans...

Page 31: ...ifferent from above select appropriate wire according to EN60204 Appendix C TABLE 5 앫 Use a tinned plating should not include zinc crimping terminal to connect the earth cable When tightening the screw be careful not to damage the threads 앫 For use as a product compliant with the Low Voltage Directive use PVC cable whose size is indicated on page 7 앫 Use the moulded case circuit breaker and magnet...

Page 32: ...equency inverter in a machine is prohibited so long until it has been confirmed that the entire machine complies with the provisions of Directive 98 37 EC from 29 12 2009 Machinery Directive 2006 42 EC During Operation In Storage During Transportation Ambient temperature 10 C to 40 50 C 10 C to 30 40 C 20 C to 65 C 20 C to 65 C The maximum temperature depends on the setting of the Pr 570 Ambient h...

Page 33: ...ximum allowable rating by US National Electrical Code Exact size must be chosen for each installation Environment Ambient temperature 10 C to 50 C 40 C for FR F746 non freezing for selected overload capability 150 Pr 570 0 10 C to 40 C 30 C for FR F746 non freezing for selected overload capability 120 Pr 570 1 Enclosure Ambient humidity 90 RH or less non condensing Storage temperature 20 C to 65 C...

Page 34: ...to the motor rated current 3 When you set the electronic thermal relay function dedicated to the Mitsubishi constant torque motor this characteristic curve applies to operation at 6 Hz or higher CAUTION 앫 Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input Avoid unnecessary reset and power OFF 앫 When using multiple motors with one invert...

Page 35: ......

Page 36: ...0 Fax 358 0 207 463 541 GREECE UTECO 5 Mavrogenous Str GR 18542 Piraeus Phone 30 211 1206 900 Fax 30 211 1206 999 HUNGARY MELTRADE Kft Fertő utca 14 HU 1107 Budapest Phone 36 0 1 431 9726 Fax 36 0 1 431 9727 LATVIA Beijer Electronics SIA Ritausmas iela 23 LV 1058 Riga Phone 371 0 784 2280 Fax 371 0 784 2281 LITHUANIA Beijer Electronics UAB Savanoriu Pr 187 LT 02300 Vilnius Phone 370 0 5 232 3101 F...

Reviews: