![Mitsubishi Electric FR-F700PJ Series Instruction Manual Download Page 195](http://html.mh-extra.com/html/mitsubishi-electric/fr-f700pj-series/fr-f700pj-series_instruction-manual_239805195.webp)
190
Frequency setting by analog input (terminal 2, 4)
4.17.5 Frequency setting signal (current) bias/gain adjustment method
(a) Method to adjust any point by application of a voltage (current) across terminals 2 and 5 (4 and 5).
Follow the following procedure to adjust the bias and gain of the frequency setting voltage (current) using the operation
panel.
for the details of parameters.
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
The inverter should be at a stop.
The inverter should be in the PU operation
mode.
(Using )
2.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Press
to display
.
5.
Turn
until
(
) appears.
Set to
C4
Terminal 2 frequency setting gain.
Terminal 2 input is
selected
Terminal 4 input is
selected
6.
Press
to display the analog voltage
(current) value (%).
Analog voltage (current)
value (%) across terminals 2
and 5 (across terminals 4
and 5)
7.
Apply a 5V (20mA) voltage (current).
(Turn the external potentiometer connected
across terminals 2 and 5 (across terminals 4
and 5) to maximum (any position).)
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
8.
Press
to set.
Terminal 2 input is
selected
Terminal 4 input is
selected
Flicker...Parameter setting complete!!
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
If the frequency meter (display meter) connected across the terminals FM and SD does not indicate exactly 60Hz, set the
calibration parameter C0 FM terminal calibration
.
If the gain and bias of frequency setting voltage (current) are too close, an error (
) may be displayed at setting.
C0 to C25 settings
are enabled.
Hz
A
Hz
A
NOTE
After performing operation in step 6, do not touch
until completion of calibration.
Hz
A
Summary of Contents for FR-F700PJ Series
Page 13: ...IX MEMO ...
Page 29: ...16 MEMO ...
Page 76: ...63 MEMO ...
Page 299: ...294 MEMO ...