4.2.18 Automatic torque boost (Pr. 38, Pr. 39)
Pr. 38 "automatic torque boost"
Pr. 39 "automatic torque boost operation starting current"
Used to detect the load current to control the output voltage (torque) of the inverter automatically.
Parameter Number
Factory Setting
Setting Range
Setting Capacity
38
0
0 to 200
Set the boost compensation (%).
Setting "0" makes the automatic torque boost inoperative.
Normally set "100" (%) to make the automatic torque boost
operative
39
0
0 to 500
Set the automatic torque boost operation starting current (A).
Normally set "0" (A).
4.2.19 Up-to-frequency sensitivity (Pr. 41)
Pr. 41 "up-to-frequency sensitivity"
The ON range of the up-to-frequency signal (SU) output when the output frequency reaches the running
frequency can be adjusted between 0 and
±
100% of the running frequency.
This parameter can be used to ensure that the running frequency has been reached or used as the operation
start signal etc. for related equipment.
Parameter
Number
Factory
Setting
Setting Range
41
10%
0 to 100%
ON
Pr.41
Output signal
SU
O
u
tput
f
requ
enc
y
(Hz
)
Running frequency
Adjustable range
Time
OFF
OFF
Note: 1. When terminal assignment is changed using Pr. 190 to Pr. 195, the other functions may be
affected. Check the functions of the corresponding terminals before making setting.
Pr. 190 to Pr. 195
(output terminal function selection)
Related parameters