PARAMETERS
69
4.2.2 Output frequency range (Pr. 1, Pr. 2)
Pr. 1 "maximum frequency"
Pr. 2 "minimum frequency"
Used to clamp the upper and lower limits of the output frequency.
#
Can be used to set the upper and lower limits of motor speed.
Parameter
Number
Factory
Setting
Setting Range
1
120Hz
0 to 120Hz
2
0Hz
0 to 120Hz
Pr.1
Pr.2
5,10V
0
Frequency setting
Output frequency
(Hz)
(20mA)
(4mA)
<Setting>
•
Use Pr. 1 to set the upper limit of the output frequency. If the frequency of the frequency command entered
is higher than the setting, the output frequency is clamped at the maximum frequency.
•
Use Pr. 2 to set the lower limit of the output frequency.
Note: When the frequency setting analog signal is used to run the motor beyond 60Hz, change the Pr. 903
and Pr. 905 values. If Pr. 1 is only changed, the motor cannot run beyond 60Hz.
CAUTION
When the Pr. 2 setting is higher than the Pr. 13 "starting frequency" value, note that the
motor will run at the preset frequency according to the acceleration time setting by
merely switching the start signal on, even if the command frequency has not been
entered.
4
Pr. 13 "starting frequency"
Pr. 903 "frequency setting voltage gain"
Pr. 905 "frequency setting current gain"
Related parameters
Summary of Contents for FR-F500 Series
Page 221: ......