PARAMETERS
66
Func-
tion
Parameter
Number
Name
Setting Range
Minimum
Setting
Increments
Factory
Setting
〈〈〈〈
EC
Version
〉〉〉〉
Refer
To
Page:
Cust-
omer
Set-
ting
$
240
Soft-PWM setting
0, 1
1
1
100
Sub
func
ti
ons
$
244
Cooling fan operation selection
0, 1
1
0
145
251
Output phase failure protection selection
0, 1
1
1
145
252
Override bias
0 to 200%
0.1%
50%
146
Addit
ional f
unc
ti
on
253
Override gain
0 to 200%
0.1%
150%
146
500
Auxiliary motor operation selection
0 to 3
1
0
147
501
Motor switch-over selection
0 to 2
1
0
147
502
MC switching interlock time
0 to 100s
0.1s
1s
147
503
Start waiting time
0 to 100s
0.1s
1s
147
504
Auxiliary motor connection-time
deceleration time
0 to 3600s
0.1s/0.01s
1s
147
505
Auxiliary motor disconnection-time
acceleration time
0 to 3600s, 9999
0.1s/0.01s
1s
147
506
Output stop detection time
0 to 3600s, 9999
0.1s/0.01s
9999
147
507
Output stop detection level
0 to 120Hz
0.01Hz
0Hz
147
508
Output stop cancel process value level
0 to 100%
0.1%
100%
147
509
Auxiliary motor 1 starting frequency
0 to 120Hz
0.01Hz
60Hz
〈
50Hz
〉
147
510
Auxiliary motor 2 starting frequency
0 to 120Hz
0.01Hz
60Hz
〈
50Hz
〉
147
511
Auxiliary motor 3 starting frequency
0 to 120Hz
0.01Hz
60Hz
〈
50Hz
〉
147
512
Auxiliary motor 1 stopping frequency
0 to 120Hz
0.01Hz
0Hz
147
513
Auxiliary motor 2 stopping frequency
0 to 120Hz
0.01Hz
0Hz
147
514
Auxiliary motor 3 stopping frequency
0 to 120Hz
0.01Hz
0Hz
147
515
Auxiliary motor start delay time
0 to 3600s
0.1s
5s
147
Adv
anc
ed PI
D
c
ont
rol f
unc
ti
ons
(N
ot
e 5)
516
Auxiliary motor stop delay time
0 to 3600s
0.1s
5s
147
$
900
FM terminal calibration
158
$
901
AM terminal calibration
158
$
902
Frequency setting voltage bias
0 to 10V
0 to 60Hz
0.01Hz
0V
0Hz
160
$
903
Frequency setting voltage gain
0 to 10V
1 to
120Hz
0.01Hz
5V
60Hz
〈
50Hz
〉
160
$
904
Frequency setting current bias
0 to 20mA
0 to 60Hz
0.01Hz
4
mA
0Hz
160
C
a
librat
ion f
unc
ti
ons
$
905
Frequency setting current gain
0 to 20mA
1 to
120Hz
0.01Hz
20
mA
60Hz
〈
50Hz
〉
160
$
990
PU buzzer control
0, 1
1
1
165
Addit
ional f
unc
ti
on
991
Parameter for option (FR-PU04)
Note: 1. The setting depends on the inverter capacity.
2. Can be accessed when Pr. 29 = 3.
3. The half-tone screened parameters allow their settings to be changed during operation if 0
(factory setting) has been set in Pr. 77. (Note that the Pr. 72 and Pr. 240 settings cannot be
changed during external operation.)
The parameters which can be changed whilst the inverter is running will also depend upon the
setting of Pr. 160 “user group read selection”.
4. The setting depends on the inverter capacity: (0.75K)/(1.5K to 3.7K)/(5.5K, 7.5K)/(11K or more).
5. Setting may be made for the NA and EC versions only.
Parameter List