PARAMETERS
64
Func-
tion
Parameter
Number
Name
Setting Range
Minimum
Setting
Increments
Factory
Setting
〈〈〈〈
EC
Version
〉〉〉〉
Refer
To
Page:
Cust-
omer
Set-
ting
107
V/F4 (fourth frequency voltage)
0 to 1000V
0.1V
0
110
108
V/F5 (fifth frequency)
0 to 120Hz, 9999
0.01Hz
9999
110
5-point
f
lex
ible V/
F
ch
a
ra
cte
ri
sti
cs
109
V/F5 (fifth frequency voltage)
0 to 1000V
0.1V
0
110
117
Communication station number
0 to 31
1
0
111
118
Communication speed
48, 96, 192
1
192
111
119
Stop bit length/data length
0, 1 (data length 8)
10, 11 (data length 7)
1
1
111
120
Parity check presence/absence
0, 1, 2
1
2
111
121
Number of communication retries
0 to 10, 9999
1
1
111
122
Communication check time interval
0, 0.1 to 999.8 s, 9999
0.1 s
0
〈
9999
〉
111
123
Waiting time setting
0 to 150ms, 9999
1ms
9999
111
C
o
m
m
unic
a
ti
on f
unc
ti
ons
124
CR
•
LF presence/absence selection
0,1,2
1
1
111
128
PID action selection
10, 11, 20, 21
(30, 31 Note 5)
10
122
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
122
130
PID integral time
0.1 to 3600 s, 9999
0.1 s
1 s
122
131
Upper limit
0 to 100%, 9999
0.1%
9999
122
132
Lower limit
0 to 100%, 9999
0.1%
9999
122
133
PID action set point for PU operation
0 to 100%
0.01%
0%
122
PI
D
c
ont
rol
134
PID differential time
0.01 to 10.00 s, 9999
0.01 s
9999
122
135
Commercial power supply-inverter
switch-over sequence output terminal
selection
0, 1
1
0
129
136
MC switch-over interlock time
0 to 100.0 s
0.1 s
1.0 s
129
137
Start waiting time
0 to 100.0 s
0.1 s
0.5 s
129
138
Commercial power supply-inverter
switch-over selection at alarm
occurrence
0, 1
1
0
129
C
o
m
m
e
rc
ial pow
er s
upply
-
in
v
e
rt
e
r sw
itch
-o
v
e
r
139
Automatic inverter-commercial power
supply switch-over frequency
0 to 60.00Hz, 9999
0.01Hz
9999
129
140
Backlash acceleration stopping
frequency (Note 2)
0 to 120Hz
0.01Hz
1.00Hz
81
141
Backlash acceleration stopping time
(Note 2)
0 to 360 s
0.1 s
0.5 s
81
142
Backlash deceleration stopping
frequency (Note 2)
0 to 120Hz
0.01Hz
1.00Hz
81
B
a
ckl
a
s
h
143
Backlash deceleration stopping time
(Note 2)
0 to 360 s
0.1 s
0.5 s
81
Di
s
p
la
y
144
Speed setting switch-over
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1
4
84
145
Parameter for option (FR-PU04)
148
Stall prevention operation level at 0V
input
0 to 150%
0.1%
120%
79
Addit
ional f
unc
ti
ons
149
Stall prevention operation level at 10V
input
0 to 150%
0.1%
150%
79
Parameter List
Summary of Contents for FR-F500 Series
Page 221: ......