INSTALLATION AND WIRING
43
(2) Low Voltage Directive
1) Our view of transistorized inverters for the Low Voltage Directive
Transistorized inverters are covered by the Low Voltage Directive (compliant with Standard DIN VDE0160).
2) Compliance
We have self-confirmed our inverters as products compliant to the Low Voltage Directive and place the CE
mark on the inverters.
3) Outline of instructions
* In the 400V class inverters, the rated input voltage range is three-phase, 380V to 415V, 50Hz/60Hz.
* Connect the equipment to the earth (ground) securely. Do not use an earth leakage circuit breaker as an
electric shock protector without connecting the equipment to the earth (ground).
* Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)
* The wire size on pages 13 and 16 are shown for following conditions.
•
Ambient Temp:
40°C (104°F) maximum
•
Wire installation:
On wall without duct or conduits
If conditions are different from above, select appropriate wire according to EN60204 ANNEX C TABLE 5.
* Use the no-fuse breaker and magnetic contactor which conform to the EN or IEC Standard.
* Use the breaker of type B (breaker that can detect both AC and DC). If not, provide double or enhanced
insulation between the inverter and other equipment, or put a transformer between the main power
supply and inverter.
* Use the inverter under the conditions of overvoltage category II and contamination level 2 or less set forth
in IEC664.
(a) To meet the overvoltage category II, insert an EN or IEC standard-compliant insulating transformer
or surge suppressor in the input of the inverter.
(b) To meet the contamination level 2, install the inverter in a control box protected against ingress of
water, oil, carbon, dust, etc. (IP54 or higher).
* In the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (The relay
outputs are basically isolated from the inverter's internal circuitry.)
* The terminals indicated as the control circuit input and output terminals on page 9 are isolated safely from
the main circuit.
Environment
During operation
In storage
During transportation
Ambient Temperature
-10°C to +50°C
(14°F to 122°F)
-20°C to +65°C
(-4°F to 149°F)
-20°C to +65°C
(-4°F to 149°F)
Ambient Humidity
90% RH or less
90% RH or less
90% RH or less
Maximum Altitude
1,000 m
(3280.80feet)
1,000 m
(3280.80feet)
10,000 m
(32808.00feet)
Details are given in the technical information "Low Voltage Directive Conformance Guide" (information
number BCN-A21041-203). Please contact your sales representative.