INSTALLATION AND WIRING
18
2.2.3 Wiring of the control circuit
(1) Wiring instructions
1) Terminals 5, SD and SE are common to the I/O signals and isolated from each other. Do not earth
(ground) these terminals. Avoid connecting the terminal SD and 5 and the terminal SE and 5.
2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the
main and power circuits (including the 200V relay sequence circuit).
3) The frequency-input signals to the control circuit are micro currents. When contacts are required, use two
or more parallel micro signal contacts or a twin contact to prevent a contact fault.
4) It is recommended to use the cables of 0.75mm
2
gauge for connection to the control circuit terminals.
If the cable gauge used is 1.25mm
2
or more, the front cover may be lifted when there are many cables
running or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.
(2) Terminal block layout
••••
Japanese and NA version
In the control circuit of the inverter, the terminals are arranged as shown below:
Terminal screw size: M3.5
Tightening torque: 1.2 N
⋅
m
A
RL
SE RUN SU
IPF
OL
FU
SD
STF STR JOG
CS
RM
RH
RT
AU STOP MRS RES
SD
FM
B
C
PC
AM
10E
10
2
5
4
1
••••
EC version
Terminal screw size: M3.5
Tightening torque: 1.2 N
⋅
m
A
SE RUN SU
LPF
OL
STOP MRS RES
PC
STF
B
C
SD
AM 10E
10
2
5
4
1
RL
RM
RH
RT
AU
STR JOG
CS
FM
SD
FU
2