2. Basic Operation
2.6 Basic operation procedure (External operation)
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
•
Pr.178 STF/DI0 terminal function selection
must be set to "60" (or
Pr.179 STR/DI1 terminal function selection
must be
set to "61") (initial value).
• Setting
Pr.79 Operation mode selection
= "3" enables multi-speed operation.
• If the STOP/RESET key on the operation panel is pressed during the External operation, the inverter stops and the PU stop
warning is activated ("PS" appears on the LCD display of the operation panel.) To reset the PU stop warning, turn OFF the
start switch (STF or STR signal), and then press the PU/EXT key. (Refer to
.)
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)
,
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selection
Pr.79 Operation mode selection
2.6.2
Setting the frequency and giving a start command
with switches (multi-speed setting) (Pr.4 to Pr.6)
• Turn ON the STF/STR signal to give a start command.
• Turn ON the RH, RM, or RL signal to give a frequency command (multi-speed setting).
[Connection diagram]
The following shows the procedure to operate at a high speed (60 Hz).
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Setting the frequency
Turn ON the high-speed switch (RH signal).
3.
Start
→
acceleration
→
constant speed
Turn ON the start switch (STF/STR signal). The frequency value on the monitor increases according to the setting
of
Pr.7 Acceleration time
, and "60.00" (60.00 Hz) appears on the monitor. The RUN LED is ON during forward
rotation and blinks slowly during reverse rotation. When the RM signal is turned ON, 30 Hz is displayed. When the
RL signal is turned ON, 10 Hz is displayed.
4.
Deceleration
→
stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of
Pr.8 Deceleration time
, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. The RUN LED
turns OFF. Turn OFF the high-speed switch (RH signal).
Forward rotation start
RM
STF
STR
RH
SD
RL
Inverter
Switch
Reverse rotation start
High speed
Middle speed
Low speed
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
RH
RM
RL
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...