161
8. (E) Environment Setting Parameters
8.2 Reset selection / disconnected PU detection / PU stop selection
1
2
3
4
5
6
7
8
9
10
8.2
Reset selection / disconnected PU detection / PU
stop selection
The reset input acceptance, disconnected PU connector detection function, and PU stop function can be selected.
The parameters above do not return to their initial values even if Parameter clear/All parameter clear is executed.
Reset selection (P.E100)
• While
P.E100
= "1", or
Pr.75
= "1, 3, 15, 17, 10001, 10003, 10015, or 10017", the reset command input is enabled (using
the RES signal or through communication) only when the protective function is activated.
Pr.
Name
Initial value
Setting range
Description
75
Reset selection/
disconnected PU
detection/PU stop
selection
[E800(-E)]
14
[E800-SCE]
10014
[E800(-E)]
0 to 3, 14 to 17
In the initial setting, the reset command input is always
enabled, the inverter operation continues even when PU is
disconnected, the operation can be stopped on the PU, and
the reset limit function is disabled.
[E800-SCE]
0 to 3, 14 to 17, 10000 to
10003, 10014 to 10017
In the initial setting, the reset command input is always
enabled, the inverter operation continues even when PU is
disconnected, the operation can be stopped on the PU, and
the reset limit function is enabled.
E100
Reset selection
0
0
Reset input is always enabled.
1
Reset input is enabled only when the protective function is
activated.
E101
Disconnected PU
detection
0
0
Operation continues even when the PU is disconnected.
1
The inverter output is shut off when the PU is disconnected.
E102
PU stop selection
1
0
The inverter decelerates to stop when the STOP key on the
PU is pressed in PU operation mode. (The PU stop function is
disabled.)
1
The inverter decelerates to stop when the STOP key on the
PU is pressed in any operation mode of the PU, external, or
Network. (The PU stop function is enabled.)
E107
Reset limit
[E800(-E)]
0
[E800-SCE]
10
0
Disabled
10 [E800-SCE]
Enabled
Pr.75 setting
Reset input
Operation after PU
disconnection is
detected
PU stop function
Reset limit
0
Always enabled.
Operation continues.
Disabled
Disabled
1
When the protective function is activated. Operation continues.
Disabled
2
Always enabled.
Inverter output shutoff
Disabled
3
When the protective function is activated. Inverter output shutoff
Disabled
14
Always enabled.
Operation continues.
Enabled
15
When the protective function is activated. Operation continues.
Enabled
16
Always enabled.
Inverter output shutoff
Enabled
17
When the protective function is activated. Inverter output shutoff
Enabled
10000
Always enabled.
Operation continues.
Disabled
Enabled
10001
When the protective function is activated. Operation continues.
Disabled
10002
Always enabled.
Inverter output shutoff
Disabled
10003
When the protective function is activated. Inverter output shutoff
Disabled
10014
Always enabled.
Operation continues.
Enabled
10015
When the protective function is activated. Operation continues.
Enabled
10016
Always enabled.
Inverter output shutoff
Enabled
10017
When the protective function is activated. Inverter output shutoff
Enabled
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...