Causes and corrective actions
Troubleshooting
7 - 8
Alarm
When an alarm occurs, the output is not shut off. You can also output an alarm signal by making pa-
rameter setting. (Set "98" in any of Pr. 190 to Pr. 192 "Output terminal function selection". Refer to sec-
tion 6.10.5).
Operation panel
indication
UV
FR-PU04
FR-PU07
—
Name
Undervoltage
Description
If the power supply voltage of the inverter decreases, the control circuit will not perform normal
functions. In addition, the motor torque will be insufficient and/or heat generation will increase.
To prevent this, if the power supply voltage decreases below about 230 V AC, this function stops
the inverter output and displays. An alarm is reset when the voltage returns to normal.
Check point
Check that the power supply voltage is normal.
Corrective action
Check that the power supply voltage is normal.
Operation panel
indication
SA
FR-PU04
FR-PU07
—
Name
Safety stop
Description
Appears when safety stop function is activated (during output shutoff ).
Check point
Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not
using the safety stop function.
Corrective action
앫
When not using the safety stop function, short across terminals S1 and P and across S2 and
SC with shorting wire for the inverter to run.
앫
If SA is indicated when across S1 and SC and across S2 and PC are both shorted while using
the safety stop function (drive enabled), internal failure might be the cause.
앫
Check the wiring of terminals S1, S2 and SC and contact your sales representative if the
wiring has no fault.
Operation panel
indication
FN
FR-PU04
FR-PU07
FN
Name
Fan fault
Description
For the inverter that contains a cooling fan, "FN" appears on the operation panel when the cool-
ing fan stops due to an alarm or different operation from the setting of Pr. 244 "Cooling fan oper-
ation selection".
Check point
Check the cooling fan for an alarm.
Corrective action
Replace the cooling fan.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......