Communication operation and setting
Parameter
6 - 234
6.19.2
Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 120,
Pr. 123, Pr. 124, Pr. 549)
Used to perform required settings for RS-485 communication between the inverter and personal
computer. Use PU connector of the inverter for communication.
●
You can perform parameter setting, monitoring, etc. using Mitsubishi inverter protocol or Mod-
bus®-RTU protocol.
●
To make communication between the personal computer and inverter, initialization of the com-
munication specifications must be made to the inverter. Data communication cannot be made if
the initial settings are not made or there is any setting error.
PU connector communication related parameter
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햲
When "1" (Modbus®-RTU protocol) is set in Pr. 549, the setting range within parenthesis is
applied.
Pr. No.
Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
117
PU communication station
number
0
0–31
(0–247)
햲
Specify the inverter station number.
Set the inverter station numbers when two or
more inverters are connected to one personal
computer.
—
118
PU communication speed
192
48/96/
192/384
Set the communication speed.
The setting value × 100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is "192".
119
PU communication stop bit
length
1
Stop bit length
Data length
0
1 bit
8 bits
1
2 bits
10
1 bits
7bits
11
2 bits
120
PU communication parity check
2
0
Without parity check
1
With odd parity check
2
With even parity check
123
PU communication waiting time
setting
9999
0–150 ms
Set the waiting time between data
transmission to the inverter and response.
9999
Set with communication data.
124
PU communication
CR/LF presence/absence
selection
1
0
Without CR/LF
1
With CR
2
With CR/LF
549
Protocol selection
0
0
Mitsubishi inverter (computer link operation)
protocol
1
Modbus®-RTU protocol
NOTE
Always reset the inverter after making the initial settings of the parameters. After you have
changed the communication-related parameters, communication cannot be made until the
inverter is reset.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......