Inspection
Maintenance and inspection
8 - 8
●
Reinstallation of the fan
After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of
"AIR FLOW" faces up.
Reconnect the fan connectors. When wiring, use care to avoid the cables being caught by
the fan.
Reinstall the fan cover. Insert hooks into the holes
. Insert hooks
until you hear a click
sound.
Fig. 8-4:
Orientation of the fan
I001864E
NOTE
Installing the fan in the opposite air flow direction can cause the inverter life to be shorter.
I001865E, I001866E
Fig. 8-5:
Connection of the fan
I002008E
Fig. 8-6:
Reinstall the fan cover
Fan side face
AIR FLOW
FR-D720S-070SC and 100SC,
FR-D740-080SC or less
FR-D740-120SC or more
FR-D720S-070SC and 100SC,
FR-D740-080SC or less
FR-D740-120SC or more
Example for FR-D740-036SC
Example for FR-D740-160SC