Communication operation and settings
Parameter
6 - 218
To read/write C3 (Pr. 902) and C6 (Pr. 904) after inverter reset or parameter clear, execute from
step
again.
쑶
●
List of calibration parameters
Example
쑴
When reading the C3 (Pr. 902) and C6 (Pr. 904) settings from the inverter of station No. 0.
Computer Send Data
Inverter Send Data
Description
ENQ 00 FF 0 01 82
ACK 00
Set "H01" to the extended link parameter.
ENQ 00 EC 0 01 7E
ACK 00
Set "H01" to second parameter changing.
ENQ 00 5E 0 0F
STX 00 0000 ETX 25
C3 (Pr. 902) is read. 0% is read.
ENQ 00 60 0 FB
STX 00 0000 ETX 25
C6 (Pr. 904) is read. 0% is read.
Tab. 6-58:
Example for data transmission
Pr.
Name
Instruction
Code
Pr.
Name
Instruction
Code
Read
Write
Extended
Read
Write
Extended
C2
(902)
Terminal 2 frequency setting
bias frequency
5E
DE
1
C5
(905)
Terminal 4 frequency setting
bias frequency
60
E0
1
C3
(902)
Terminal 2 frequency setting
bias
5E
DE
1
C6
(904)
Terminal 4 frequency setting
bias
60
E0
1
125
(903)
Terminal 2 frequency setting
gain frequency
5F
DF
1
126
(905)
Terminal 4 frequency setting
gain frequency
61
E1
1
C4
(903)
Terminal 2 frequency setting
gain
5F
DF
1
C7
(905)
Terminal 4 frequency setting
gain
61
E1
1
Tab. 6-59:
Calibration parameters
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......