Basic settings
Simple mode parameter list
FR-D700 SC EC
5 - 11
5.1.6
Operation mode selection (Pr. 79)
Select the operation command location and frequency command location.
For the terminal used for the X12 signal (PU operation interlock signal) input, assign "12" in
Pr. 178 to Pr. 182 "Input terminal function selection" to assign functions (refer to section
6.9.1). When the X12 signal is not assigned, function of the MRS signal switches from MRS
(output stop) to PU operation interlock signal.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
LED Indication
79
Operation
mode
selection
0
0
External/PU switch over mode
Press the PU/EXT key to switch between the PU and
external operation mode. (Refer to section 4.3.3.)
At power on, the inverter is in the external operation
mode.
1
PU operation mode
2
Fixed to external operation mode
Operation can be performed by switching between the
external and Net operation mode.
3
External/PU combined operation mode 1
Running frequency
Start signal
Operation panel and PU
(FR-PU04/FR-PU07) set-
ting or external signal
input (multi-speed set-
ting, across terminals 4-5
(valid when AU signal
turns on)).
External signal input
(terminal STF-, STR)
4
External/PU combined operation mode 2
Running frequency
Start signal
External signal input (Ter-
minal 2, 4, JOG, multi-
speed selection, etc.)
Input using the RUN key
of the operation panel or
FWD/REV of the PU
(FR-PU04/FR-PU07)
6
Switch-over mode
Switch among PU operation, external operation, and
NET operation while keeping the same operation sta-
tus.
7
External operation mode (PU operation interlock)
X12 signal ON
:
Operation mode can be switched to the PU operation
mode.
(output stop during external operation)
X12 signal OFF
:
Operation mode can not be switched to the PU opera-
tion mode.
NOTE
Setting values 0, 1, 2, 3 and 4 for Pr. 79 can be changed in the easy operation mode. (Refer
to section 4.3.3.)
: OFF
: ON
External operation mode
PU operation mode
External operation mode
NET operation mode
External operation mode
NET operation mode
PU operation mode
External operation mode
PU operation mode
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......