Simple mode parameter list
Basic settings
5 - 4
5.1.2
When the rated motor frequency is 60Hz (Pr. 3)
First, check the motor rating plate. If a frequency given on the rating plate is "60Hz" only, always
set Pr. 3 "Base frequency" to "60Hz". Leaving the base frequency unchanged from "50Hz" may
make the voltage low and the torque insufficient. It may result in an inverter trip due to overload.
쑶
Pr.
No.
Name
Initial Value
Setting
Range
Description
3
Base frequency
50Hz
0–400Hz
Set the rated motor frequency.
Example
쑴
Change Pr. 3 "Base frequency" to 60Hz according to the motor rated frequency.
I001745E
Fig. 5-2:
Setting the base frequency
V/F
V/F
V/F
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.3 (Pr. 3) appears.
Press the SET key to show the currently set value.
The initial value "50.00" (50Hz) appears.
Turn the digital dial to change it to the setting
value of "60.00".
Press the SET key to set.
Operation
Display
The parameter number
read previously
appears.
Flicker ... Parameter setting complete!
PU indication is lit.
By turning the digital dial, you can read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
PRM indication is lit.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......