Simple mode parameter list
Basic settings
5 - 2
5.1.1
Overheat protection of the motor by the inverter
Set this parameter when using a motor other than the Mitsubishi standard motor (SF-JR) and
Mitsubishi constant torque motor (SF-HRCA). Set the rated motor current in Pr. 9 "Electronic
thermal O/L relay" to protect the motor from overheat.
Refer to appendix A for the rated inverter current value.
쑶
Pr. No. Name
Initial Value
Setting Range
Description
9
Electronic thermal O/L
relay
Rated inverter
current
0–500A
Set the rated motor current.
Example
쑴
Change the Pr. 9 "Electronic thermal O/L relay" setting to 5A according to the motor rated
current.
I002011E
Fig. 5-1:
Setting of the electronic thermal O/L relay
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.9 (Pr. 9) appears.
Press the SET key to show the currently set value.
The initial setting "8.00A" (for FR-D740-080SC
as an example) appears.
Turn the digital dial clockwise to change the set
value to "5.00" (5A).
Press the SET key to set.
Operation
Display
The parameter number read previously appears.
Flicker ... Parameter setting complete!
PU indication is lit.
Refer to appendix A
for the rated inverter
current value.
By turning the digital dial, you can read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
PRM indication is lit.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......