Selection of operation mode and operation location
(10) Switching of operation mode by external (X16) signal
When External operation and operation from the operation panel are used together, use of the PU-External operation
switchover (X16) signal allows switching between the PU operation mode and External operation mode during a stop
(during a motor stop, start command OFF).
When
Pr. 79
= any of "0, 6, 7", the operation mode can be switched between the PU operation mode and External
operation mode. (
Pr. 79
= "6" At Switchover mode, operation mode can be changed during operation)
For the terminal used for X16 signal input, set "16" to any of
Pr. 178 to Pr. 182 (input terminal function selection)
to assign the
function.
NOTE
If the X12 (MRS) signal is ON, the operation mode cannot be switched to the PU operation mode when the start signal
(STF, STR) is ON.
When the MRS signal is used as the PU interlock signal, the MRS signal serves as the normal MRS function (output
stop) by turning ON the MRS signal and then changing the
Pr. 79
value to other than "7" in the PU operation mode. As
soon as "7" is set to
Pr. 79
, the MRS signal acts as the PU interlock signal.
When the MRS signal is used as the PU interlock signal, the logic of the signal is as set in
Pr. 17
. When
Pr. 17
= "2",
read ON as OFF and OFF as ON in the above explanation.
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Pr. 79
Setting
X16 Signal State Operation Mode
Remarks
ON (External)
OFF (PU)
0 (initial value)
External operation
mode
PU operation mode Can be switched to External, PU or NET operation mode
1
PU operation mode
Fixed to PU operation mode
2
External operation mode
Fixed to External operation mode (can be switched to NET operation
mode)
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
External operation
mode
PU operation mode
Switching among the External, PU, and NET operation mode is
enabled while running.
7
X12 (MRS)
ON
External operation
mode
PU operation mode
Can be switched to External, PU or NET operation mode (output stop
in External operation mode)
X12 (MRS)
OFF
External operation mode
Fixed to External operation mode (forcibly switched to External
operation mode)
REMARKS
The operation mode status changes depending on the setting of
Pr. 340 Communication startup mode selection
and the ON/OFF
status of the X65 and X66 signals. (For details, refer to
page
)
The priorities of
Pr. 79
,
Pr. 340
and signals are
Pr. 79
X12
X66
X65
X16
Pr. 340
.
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.