Adjustment of the output torque (current) of the motor
(2) Setting of stall prevention operation level
(Pr. 22)
(3) Stall prevention operation signal output and output timing adjustment (OL signal,
Pr. 157
)
When the output current exceeds the stall prevention operation level and stall prevention is activated, the stall prevention
operation signal (OL signal) turns ON for longer than 100ms. When the output current falls to or below the stall prevention
operation level, the output signal turns OFF.
Use
Pr. 157 OL signal output timer
to set whether the OL signal is output immediately or after a preset period of time.
This operation is also performed when the regeneration avoidance function or
(overvoltage stall) is executed.
For the OL signal, set "3 (positive logic) or 103 (negative logic)" in
Pr. 190
,
Pr. 192 or Pr. 197 (output terminal function
selection)
and assign functions to the output terminal.
Set in
Pr. 22
the percentage of the output current to the rated
inverter current at which stall prevention operation will be
performed. Normally set this parameter to 150% (initial value).
Stall prevention operation stops acceleration (makes
deceleration) during acceleration, makes deceleration during
constant speed, and stops deceleration (makes acceleration)
during deceleration.
When stall prevention operation is performed, the OL signal is
output.
NOTE
If an overload status lasts long, an inverter trip (e.g. electronic thermal O/L relay (E.THM)) may occur.
Pr. 157
Setting
Description
0
(initial value)
Output immediately.
0.1 to 25
Output after the set time (s) has elapsed.
9999
Not output.
NOTE
If the frequency has fallen to 1Hz by stall prevention operation and remains for 3s, a fault (E.OLT) appears to trip the
inverter output.
Changing the terminal assignment using
Pr. 190, Pr. 192, and Pr. 197 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Stall prevention operation example
Pr. 22
OL
Output current
Acceleration
Time
Constant
speed
Deceleration
Output frequency
Overload state (OL operation)
OL output signal
Pr. 157
set time(s)
Summary of Contents for FR-D710W-0.1K
Page 45: ...36 MEMO ...
Page 61: ...52 MEMO ...
Page 254: ...252 MEMO ...
Page 296: ...294 MEMO ...
Page 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Page 312: ...4 4 BCN C22005 689 MEMO ...