19
Main circuit terminal specifications
(3) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
100V, 200V class
400V class
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor
terminals, deteriorating the insulation of the motor. If that is the case, use a "400V class inverter-driven insulationenhanced
motor" and set a frequency in
Pr. 72 PWM frequency selection
according to the total wiring length shown in the following table.
(Refer to page 84 to drive a 400V class motor with an inverter.)
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
0.1K
0.2K
0.4K
0.75K
1.5K or
higher
1 (1kHz) or less
200m
200m
300m
500m
500m
2 to15
(2kHz to 14.5kHz)
30m
100m
200m
300m
500m
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
0.4K
0.75K
1.5K
2.2K
3.7K or
higher
1 (1kHz) or less
200m
200m
300m
500m
500m
2 to15
(2kHz to 14.5kHz)
30m
100m
200m
300m
500m
Total wiring length when using a general-purpose motor (FR-D720-1.5K or higher, FR-D720S-1.5K
or higher, FR-D740-3.7K or higher)
Wiring Length
50m or less
50m to 100m
Exceeding 100m
Pr. 72 PWM frequency selection
(Carrier frequency)
15 (14.5kHz) or less
8 (8kHz) or less
2 (2kHz) or less
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level.
(Refer to page 80 for Pr. 22 Stall prevention operation level
and
Pr. 156 Stall prevention
operation selection )
When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (
Pr. 162
= "1, 11").
Parameters referred to
Pr. 72 PWM frequency selection
300m+300m=600m
500m or less
300m
300m
Motor capacity
0.1kW
0.2kW
0.4kW or higher
Wiring length
20m
50m
100m