To use the inverter outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing
screws enclosed.
Note, the protection structure of the Inverter units is considered to be an IP00.
∗
On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
∗
The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (Relay outputs are
basically isolated from the inverter internal circuit.)
∗
Control circuit terminals on
page 4
are safely isolated from the main circuit.
∗
Environment
∗
Provide the appropriate UL and cUL listed Class T type fuse that is suitable for branch circuit protection in accordance
with the table below.
∗
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
FR-D740-080 or less
FR-D720S-070 and 100
Example for FR-D740-036
FR-D740-120 or more
Example for FR-D740-160
Running
In Storage
During Transportation
Surrounding air
temperature
-10°C to +50°C
-20°C to +65°C
-20°C to +65°C
Humidity
90% RH or less
90% RH or less
90% RH or less
Maximum Altitude
1000m
1000m
10000m
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.
FR-D740-
-EC
012
022
036
050
080
120
160
Rated fuse voltage(V)
480V or more
Fuse Maximum
allowable rating
(A)
∗
Without power factor
improving reactor
6
10
15
20
30
40
70
With power factor
improving reactor
6
10
10
15
25
35
60
FR-D720S-
-EC
008
014
025
042
070
100
Rated fuse voltage(V)
240V or more
Fuse Maximum
allowable rating
(A)
∗
Without power factor
improving reactor
15
20
20
30
40
60
With power factor
improving reactor
15
20
20
20
30
50
Fan connector
Fan
Fan cover
Fan cover
fixing screw
Fan
Fan cover
Fan cover
fixing screws
Fan connector