16
PARAMETER LIST
260
PWM frequency automatic
switchover
0, 1
0
261
Power failure stop selection
0, 1, 2
0
267
Terminal 4 input selection
0, 1, 2
0
268
Monitor decimal digits
selection
0, 1, 9999
9999
269
Parameter for manufacturer setting. Do not set.
295
Magnitude of frequency
change setting
0, 0.01, 0.10,
1.00, 10.00
0
296
Password lock level
1 to 6, 101 to
106, 9999
9999
297
Password lock/unlock
1000 to 9998
(0 to 5, 9999)
9999
298
Frequency search gain
0 to 32767,
9999
9999
299
Rotation direction detection
selection at restarting
0, 1, 9999
0
338
Communication operation
command source
0, 1
0
339
Communication frequency
command source
0, 1, 2
0
340
Communication startup mode
selection
0, 1, 10
0
342
Communication EEPROM
write selection
0, 1
0
343
Communication error count
—
0
450
Second applied motor
0, 1, 9999
9999
495
Remote output selection
0, 1, 10, 11
0
496
Remote output data 1
0 to 4095
0
502
Stop mode selection at
communication error
0, 1, 2
0
503
Maintenance timer
0 (1 to 9998)
0
504
Maintenance timer alarm
output set time
0 to 9998,
9999
9999
549
Protocol selection
0, 1
0
551
PU mode operation command
source selection
2, 4, 9999
9999
555
Current average time
0.1 to 1s
1s
556
Data output mask time
0 to 20s
0s
557
Current average value monitor
signal output reference current
0 to 500A
Rated
inverter
current
561
PTC thermistor protection level
0.5 to 30
Ω
,
9999
9999
563
Energization time carrying-
over times
(0 to 65535)
0
564
Operating time carrying-over
times
(0 to 65535)
0
571
Holding time at a start
0 to 10s,
9999
9999
575
Output interruption detection
time
0 to 3600s,
9999
1s
576
Output interruption detection
level
0 to 400Hz
0Hz
Parameter
Name
Setting
Range
Initial
Value
577
Output interruption cancel
level
900 to
1100%
1000%
592
Traverse function selection
0, 1, 2
0
593
Maximum amplitude amount
0 to 25%
10%
594
Amplitude compensation
amount during deceleration
0 to 50%
10%
595
Amplitude compensation
amount during acceleration
0 to 50%
10%
596
Amplitude acceleration time
0.1 to 3600s
5s
597
Amplitude deceleration time
0.1 to 3600s
5s
611
Acceleration time at a restart
0 to 3600s,
9999
9999
653
Speed smoothing control
0 to 200%
0
665
Regeneration avoidance
frequency gain
0 to 200%
100
872
∗6
Input phase loss protection
selection
0, 1
1
882
Regeneration avoidance
operation selection
0, 1, 2
0
883
Regeneration avoidance
operation level
300 to 800V
400VDC/
780VDC
∗5
885
Regeneration avoidance
compensation frequency limit
value
0 to 10Hz,
9999
6Hz
886
Regeneration avoidance
voltage gain
0 to 200%
100%
888
Free parameter 1
0 to 9999
9999
889
Free parameter 2
0 to 9999
9999
891
Cumulative power monitor digit
shifted times
0 to 4, 9999
9999
C1
(901)
∗4
AM terminal calibration
-
-
C2
(902)
∗4
Terminal 2 frequency setting
bias frequency
0 to 400Hz
0Hz
C3
(902)
∗4
Terminal 2 frequency setting
bias
0 to 300%
0%
125
(903)
∗4
Terminal 2 frequency setting
gain frequency
0 to 400Hz
50Hz
C4
(903)
∗4
Terminal 2 frequency setting
gain
0 to 300%
100%
C5
(904)
∗4
Terminal 4 frequency setting
bias frequency
0 to 400Hz
0Hz
C6
(904)
∗4
Terminal 4 frequency setting
bias
0 to 300%
20%
126
(905)
∗4
Terminal 4 frequency setting
gain frequency
0 to 400Hz
50Hz
C7
(905)
∗4
Terminal 4 frequency setting
gain
0 to 300%
100%
Parameter
Name
Setting
Range
Initial
Value
D700_EC_Guideline_ib0600352ENG.book 16 ページ 2008年4月10日 木曜日 午後2時6分