WIRING
3.3 Control circuit specifications
(1) Control circuit terminal layout
(2) Wiring method
z
Wiring
Use a bar terminal and a cable with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of
the cable and apply directly.
Insert the bar terminal or the single wire into a socket of the terminal.
1) Strip off the sheath about the size below. If the length of the sheath peeled is too long, a short circuit may occur among
neighboring wires. If the length is too short, wires might come off.
2) Crimp the bar terminal.
Insert wires to a bar terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the bar terminal after crimping. Do not use a bar terminal of which the crimping is inappropriate, or
the face is damaged.
Introduced products on bar terminals :(as of Mar., 2008)
Bar terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
Wire the stripped cable after twisting it to prevent it from
becoming loose. In addition, do not solder it.
Wire Size (mm
2
)
Bar Terminal Model
Maker
With Insulation Sleeve
Without Insulation Sleeve
0.3, 0.5
AI 0,5-10WH
—
Phoenix Contact Co.,Ltd.
0.75
Al 0,75-10GY
A 0,75-10
1
AI 1-10RD
A 1-10
1.25, 1.5
AI 1,5-10BK
A 1,5-10
0.75 (for two cables)
AI-TWIN 2 X 0,75-10GY
—
STF STR
PC
SD
RH
RM
RL
AM
C
B
A
10
2
5
4
RUN SE
S1 S2 SC
SO
SD
Recommended
cable size:
0.3mm
2
to 0.75mm
2
Cable stripping size
10mm
Sleeve
Shell
Cable
Unstranded
wires
Damaged
Wires are not inserted
into the shell
Crumpled tip