(E) Environment setting parameters
88
5.2.2
Reset selection / disconnected PU detection /
reset limit
Reset selection (P.E100)
• When
P.E100
= "1" or
Pr.75
= "15, 17, 115, or 117", reset (reset command via RES signal or communication) input is
enabled only when the protective function is activated.
NOTE
• When the reset signal (RES) is input during operation, the inverter is also reset. The motor coasts since the inverter being
reset shuts off the output. Also, the cumulative value of electronic thermal O/L relay is cleared.
• The input of the operation panel reset key is only enabled when the protective function is activated, regardless of the
P.E100
and
Pr.75
settings.
Disconnected PU detection (P.E101)
• If the converter unit detects that the operation panel has been disconnected for 1 s or longer while
P.E101
= "1" or
Pr.75
=
"16, 17, 116 or 117", the protective function (E.PUE) is activated and the inverter output is shut off.
NOTE
• If the operation panel is disconnected before power-ON, the output is not shut off.
• To restart, confirm that the operation panel is connected and then reset the converter unit.
• When RS-485 communication operation is performed through the PU connector, the reset selection is valid but the
disconnected PU detection function is invalid. (The communication is checked according to
Pr.122
PU communication
check time interval
.)
The reset input acceptance, the disconnected operation panel connector detection function, and the reset limit function
can be selected.
Pr.
Name
Initial value
Setting range
Description
75
Reset selection/disconnected
PU detection/reset limit
14
14 to 17, 114 to 117
For the initial setting, reset is always
enabled, PU disconnection is not detected,
and the reset limit function is disabled.
E100
Reset selection
0
0
Reset input is always enabled.
1
Reset input is enabled only when the
protective function is activated.
E101
Disconnected PU detection
0
0
Operation continues even when the
operation panel is disconnected.
1
The inverter output is shut off when the
operation panel is disconnected.
E107
Reset limit
0
0
Reset limit is disabled.
1
Reset limit is enabled.
The parameters above will not return to their initial values even if parameter (all) clear is executed.
Pr.75
Setting value
Reset selection
Disconnected PU detection
Reset limit function
14 (initial value)
Reset input always enabled
Operation continues even when the
operation panel is disconnected.
Invalid
15
Reset input enabled only when the
protective function activated.
16
Reset input always enabled
The inverter output is shut off when
the operation panel is disconnected.
17
Reset input enabled only when the
protective function activated.
114
Reset input always enabled
Operation continues even when the
operation panel is disconnected.
Enabled
115
Reset input enabled only when the
protective function activated.
116
Reset input always enabled
The inverter output is shut off when
the operation panel is disconnected.
117
Reset input enabled only when the
protective function activated.
Summary of Contents for FR-CC2-P