(N) Operation via communication and its settings
123
5
GROUP
N
• Error code
If any error is found in the data received by the converter unit, its error definition is sent back to the computer together with
the NAK code.
Response time
Error
code
Error item
Fault definition
Converter unit operation
H0
Computer NAK error
The transmission request data from the computer was containing
errors for the permissible number of retries or more.
Output is shut off (E.PUE/
E.SER) if error occurs
continuously more than the
permissible number of retries.
H1
Parity error
The parity check result does not match the specified parity.
H2
Sum check error
The sum check code in the computer does not match that of the
data received by the converter unit.
H3
Protocol error
The data received by the converter unit has a grammatical
mistake. Or, data receive is not completed within the
predetermined time. CR or LF is not as set in the parameter.
H4
Framing error
The stop bit length differs from the initial value.
H5
Overrun
New data has been sent by the computer before the converter unit
completes receiving the preceding data.
H6
—
—
—
H7
Character error
The character received is invalid (other than 0 to 9, A to F, control
code).
Does not accept the received
data. The converter unit
output is not stopped by the
fault.
H8
—
—
—
H9
—
—
—
HA
Mode error
Parameter write was attempted in other than the computer link
operation mode, when operation command source is not selected
or during converter unit operation.
Does not accept the received
data. The fault does not
occur.
HB
Instruction code error
The specified instruction code does not exist.
HC
Data range error
Invalid data has been specified for parameter writing, etc.
HD
—
—
—
HE
—
—
—
HF
Normal (no error)
—
—
(Example 1)
Computer Converter unit
ENQ
*W
aiting
time
1
Instruction
code
Station
number
0
1
Data
E
1
0
7
A
D
F
4
H05
H30 H31
H31
H45 H31
H30 H37 H41 H44 H46 H34
Binary code
H30+H31+H45+H31+H31+H30+H37+H41+H44
= H1F4
Sum
(Example 2)
STX
Data read
Station
number
0
1
1
7
0
3
0
H02
H30 H31
H37
H31 H37
H30 H03 H33 H30
Sum
ETX
7
∗
When the
Pr. 123 Waiting time setting
"9999", create the communication request
data without "waiting time" in the data format. (The number of characters decreases by 1.)
Converter unit
ASCII Code
ASCII Code
Binary code
H30+H31+H31+H37+H37+H30
= H130
Sum
check
code
Sum
check
code
Computer
10 ms or more necessary
Computer
Converter unit
Converter unit
Computer
Data sending time (refer to the following formula)
Converter unit data processing time
Data sending time (refer to the following formula)
Waiting time
(setting 10 ms)
Data check time
(depends on the
instruction code (see the
following table))
Time