5. PARAMETERS
5.8 Parameter clear / All parameter clear
1
2
3
4
5
6
7
8
9
10
5.8
Parameter clear / All parameter clear
• Set "1" to
Pr.CLR Parameter clear
or
ALL.CL All parameter clear
to initialize all parameters. (Parameters cannot be cleared
when
Pr.77 Parameter write selection
= "1".)
• Terminal function selection parameters are not cleared even after Parameter clear has been performed.
• Refer to the parameter list on
for parameters cleared with this operation.
Operating procedure
1.
Turning ON the power of the converter unit
The operation panel is in the monitor mode.
2.
Selecting the parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
3.
Selecting a parameter number
Turn
to "
" for Parameter clear or turn it to "
" for All parameter clear, and press
. "
(initial value)" appears.
4.
Parameter clear
Turn
to change the set value to "
". Press
to enter the setting. "
" and "
"
("
") are displayed alternately after parameters are cleared.
• Turn
to read another parameter.
• Press
to show the setting again.
• Press
twice to show the next parameter.
Setting
Description
Pr.CL Parameter clear
ALL.C All parameter clear
0
Initial display (Parameters are not cleared.)
1
The settings of parameters except for terminal function
selection parameters are initialized.
The settings of all the parameters, including terminal function
selection parameters, are initialized.