7.1.4
Output Instance 127/Input Instance 177
Output instance 127 (master
→
inverter)
When using Output Instance 127, set Input Instance to 177.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AU
RT
RH
RM
RL
Fault
Reset
Run Rev
Run Fwd
1
32Bit
Format
Hz
Write
Attr
RES
STOP
MRS
CS
JOG
2
Speed/frequency setting value or writing data (16 bits: L)
Format for 16-bit data
(32Bit Format (Bit7 of
Byte1) = 0)
3
Speed/frequency setting value or writing data (16 bits: H)
4
Attribute 2 class ID (reading specified only)
5
Attribute 2 attribute ID (reading specified only)
6
Attribute 1 class ID (both reading and writing)
7
Attribute 1 attribute ID (both reading and writing)
2
Speed/frequency setting value or writing data (32 bits: LL)
Format for 32-bit data
(32Bit Format (Bit7 of
Byte1) = 1)
3
Speed/frequency setting value or writing data (32 bits: LH)
4
Writing data (32 bits: HL)
5
Writing data (32 bits: HH)
6
Attribute 1 class ID
7
Attribute 1 attribute ID