2.3 Encoder specification / terminating resistor switch setting
Encoder specification selection switch (SW3)
Select either differential line driver or complementary.
It is initially set to the differential line driver. Switch its position according
to output circuit.
Terminating resistor selection switch (SW1)
Select "ON"/"OFF" of the internal terminating resistor. Set the switch to
"ON" (initial status) when an encoder output type is differential line driver
and set to "OFF" when complementary.
ON : with internal terminating resistor (initial setting status)
OFF : without internal terminating resistor
NOTE
• Set all switches to the same setting ("ON"/ "OFF").
• If the encoder output type is differential line driver, set the
terminating resistor switch to the "OFF" position when
sharing the same encoder with other unit (CNC
(computerized numerical controller), etc) or a terminating
resistor is connected to other unit.
Complementary
Differential line driver
(initial status)
1
2
O
N
SW2
SW3
SW1
1
2
3
4
O
N
Internal terminating
resistor-ON
(initial status)
Internal terminating
resistor-OFF
1
2
O
N
SW2
SW3
SW1
1
2
3
4
O
N