(D) Operation command and frequency command
Parameters
5 - 276
PU/External combined operation mode 2 (Pr. 79 = "4")
●
Select the PU/External combined operation mode 2 when applying a frequency command from
the external potentiometer, or multi-speed and JOG signals, and inputting a start command by
key operation of the operation panel or the parameter unit.
●
Set "4" in Pr. 79. The mode cannot be changed to other operation modes.
Switchover mode (Pr. 79 = "6")
PU, External and Network operation (when RS-485 terminals or communication option is used) can be
switched among during operation.
PU operation interlock (Pr. 79 = "7")
●
The operation mode can be forcibly switched to the External operation mode by input of the PU
operation interlock (X12) signal. This function prevents the operation mode from being acciden-
tally unswitched from the PU operation mode. If the operation mode left unswitched from the PU
operation mode, the inverter does not reply to the commands sent through external commands.
●
Set Pr. 79 = "7" (PU operation interlock).
●
To input the X12 signal, set "12" in any of Pr. 178 to Pr. 189 (input terminal function selection) to
assign the function to a terminal. (For details on Pr. 178 to Pr. 189, refer to page 5-439.)
I002449E
Fig. 5-113:
Combined operation mode 2
Operation mode
switchover
Operation switchover/Operating status
External operation
➔
PU operation
Set to the PU operation mode on the operation panel and parameter unit.
앫
As the direction of rotation, the direction that was active by External operation is continued.
앫
For the setting frequency, the setting of the potentiometer (frequency command) is
continued. (Note, however, that the setting disappears when the power is turned OFF or
when the inverter is reset.)
External operation
➔
NET operation
The switchover command to the Network operation mode is transmitted via communication.
앫
As the direction of rotation, the direction that was active by External operation is continued.
앫
The setting by the setting potentiometer (frequency command) is kept. (Note, however,
that the setting disappears when the power is turned OFF or when the inverter is reset.)
PU operation
➔
External operation
Press the External operation key on the operation panel and parameter unit.
앫
The direction of operation is determined by the External operation input signal.
앫
The setting frequency is determined by the external frequency command signal.
PU operation
➔
NET operation
The switchover command to the Network operation mode is transmitted via communication.
앫
For the direction of operation and setting frequency, the status during PU operation is
continued.
NET operation
➔
External operation
The switchover command to the External operation mode is transmitted via communication.
앫
The direction of operation is determined by the External operation input signal.
앫
The setting frequency is determined by the external frequency command signal.
NET operation
➔
PU operation
Switch to the PU operation mode on the operation panel and parameter unit.
앫
For the direction of operation and frequency, the status during Network operation is
continued.
Tab. 5-103:
Operation states in the switch-over mode
5
10
2
Frequency setting
Potentiometer
Inverter
Operation panel
(FR-DU08)
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......