Basic operation procedure (External operation)
Basic operation
4 - 28
4.6.5
Setting the frequency using an analog signal (current input)
Connection diagram
NOTES
Turn ON the STF (STR) signal to give a start command.
Turn ON the AU signal.
Set Pr. 79 "Operation mode selection" = "2" (External operation mode).
I002447E_G
Fig. 4-11:
Frequency setting by analog current input
Example
Operation example: Operate at 60 Hz.
Operation
Turning ON the power of the inverter
The monitor display turns ON.
Terminal 4 input selection
Turn ON the terminal 4 input selection signal (AU). Input to the terminal 4 is enabled.
Start
Turn ON the start switch (STF or STR). [FWD] or [REV] indicator flickers as no frequency command is given.
Acceleration
➔
constant speed
Input 20 mA. The frequency value indicated on the display increases for the time set in Pr. 7 "Acceleration time", and is
fixed at "
" (60.00 Hz). [FWD] indicator turns ON during the forward rotation, and [REV] indicator turns ON
during the reverse rotation.
$
Deceleration
Input 4 mA or less. The frequency value indicated on the display decreases for the time set in Pr. 8 "Deceleration time",
and the motor stops rotating at "
" (0.00 Hz). [FWD] or [REV] indicator flickers.
%
Stop
Turn OFF the start switch (STF or STR). [FWD] or [REV] indicator turns OFF.
Tab. 4-19:
Operate the inverter by using the analog current input
NOTES
When both the forward rotation switch (STF) and the reverse rotation switch (STR) are turned ON,
the motor cannot be started. If both are turned ON while the motor is running, the motor deceler-
ates to a stop.
Pr. 184 "AU terminal function selection" must be set to "4" (initial value) (AU signal).
Parameters referred to
Pr. 7, Pr. 8
Acceleration time, Deceleration time
=>
Pr. 184
AU terminal function selection
=>
5(-)
4(+)
STF
STR
PC
AU
Inverter
Current signal
source
(4–20 mA DC)
Reverse rotation start
Switch
Forward rotation start
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......