![Mitsubishi Electric FR-A7NCA Instruction Manual Download Page 111](http://html.mh-extra.com/html/mitsubishi-electric/fr-a7nca/fr-a7nca_instruction-manual_239765111.webp)
103
OBJECT DICTIONARY
8
8.3.10 (Index 4001h) Set frequency (Set Speed) (w) /
Output frequency (Running speed) (r)
Sub Index
Item
Description
00h
Name
Number of Entries
Data type
UNSIGNED8 (8 bit unsigned)
Default value
2
Unit
Access attribute
Read Only
Availability of mapping to PDO Disable
01h
Name
Set frequency (w) / Output frequency (r)
Data type
UNSIGNED16 (16 bit unsigned)
Default value
Unit
0.01Hz (frequency)
Access attribute
Read / Write
Availability of mapping to PDO Enable
02h
Name
Set speed (w) / Running Speed (r)
Data type
UNSIGNED16 (16 bit unsigned)
Default value
Unit
1r/min (speed)
Access attribute
Read / Write
Availability of mapping to PDO Enable
A7NCA.book 103 ページ 2006年7月3日 月曜日 午前9時48分