60
4.3.5
Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)
Motor speed can be limitted.
Parameter
Number
Name
Initial Value
Setting Range
Description
1
Maximum frequency
120Hz
0 to 120Hz
Set the upper limit of the output frequency.
2
Minimum frequency
0Hz
0 to 120Hz
Set the lower limit of the output frequency.
Changing example
Limit the frequency set by the potentiometer,
etc. to 60Hz maximum.
(Set "60"Hz in
Pr. 1 Maximum frequency
.)
REMARKS
· The output frequency is clamped by the
Pr. 2
setting even if the set frequency is lower than the
Pr. 2
setting (The frequency will
not decrease to the
Pr. 2
setting.)
Note that
Pr. 15 Jog frequency
has higher priority than the minimum frequency.
· When the
Pr. 1
setting is changed, frequency higher than the
Pr. 1
setting can not be set by
.
· When performing a high speed operation at 120Hz or more, setting of
Pr. 18 High speed maximum frequency
is necessary.
(Refer to chapter 4 of
the instruction manual (applied).)
CAUTION
If the
Pr. 2
setting is higher than the
Pr. 13 Starting frequency
value, note that the motor will run at the set frequency
according to the acceleration time setting by merely switching the start signal on, without entry of the command
frequency.
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
Frequency setting
Clamped at the
maximum frequency
Clamped at the
minimum frequency
5, 10V
(20mA)
0
(4mA)
1.
Screen at powering on
The monitor display appears.
Display
Operation
3.
Press to choose the parameter
setting mode.
4.
Pr. 1
) appears.
Flicker ··· Parameter setting complete!!
7.
Press to set.
5.
Press to read the currently set value.
" "(initial value) appears.
6.
Turn to change it to the set
value " ".
PU indication is lit.
2.
Press to choose the PU operation
mode.
· Press to show the setting again.
· Press twice to show the next parameter.
· By turning , you can read another parameter.
The parameter
number read
previously appears.