352
PARAMETER
2.15.3 Reference of terminal FM/AM, terminal AM0/AM1 (FR-A7AY), terminal DA1 (FR-
A7AZ) [Pr. 55, 56, 291
*
, 839*, 866
*
, 867*]
(common)
Two types of monitor outputs are available in
: pulse train output from terminal FM and
analog voltage output from terminal AM. Analog voltage
output (terminal AM0) and analog current output (terminal
AM1) become available when the plug-in option FR-A7AY
is mounted. Bipolar analog voltage output (terminal DA1)
becomes available when the plug-in option FR-A7AZ is
mounted to
. Terminal FM for pulse output is
available for monitor output in
. Analog
voltage output (terminal AM0) and analog current output
(terminal AM1) become available when the plug-in option
FR-A7AY is mounted to
. For
, pulse train
output by voltage output and by open collector output can
be selected for terminal FM.
Set the reference of the signal output from terminal FM and
AM, AM0, AM1, DA1.
(*[Pr. 291, 839, 866] are not available for
.)
(*[Pr. 291, 839, 866, 867] are not available for
.)
common
F700
E700
D700
A700
F700
A700
E700
D700
E700
A700
[Pr. ]
Name
Initial
Value
Setting Range
Description
Available
Inverters
55
*
Frequency
monitoring reference
60Hz
0 to 400Hz
Set the full-scale value to output the output frequency
monitor value to terminal FM and AM.
{
{
{
56
*
Current monitoring
reference
Inverter
rated
output
current
55K or
less
0 to
500A
Set the full-scale value to output the output current
monitor value to terminal FM and AM.
{
{
{
75K or
more
0 to
3600A
291
Pulse train I/O
selection
0
0
Pulse train input
Pulse train output
{
—
—
Terminal JOG
FM output
1
Pulse train input
FM output
10
Terminal JOG
High speed pulse train output (50%Duty)
11
Pulse train input
High speed pulse train output (50%Duty)
20
Terminal JOG
High speed pulse train output (ON
width is always same)
21
Pulse train input
High speed pulse train output (ON
width is always same)
100
Pulse train input
High speed pulse train output (ON width
is always same)
The inverter outputs the signal input as
pulse train as is
839
DA1 output filter
0.05s
0 to 5s
Set the output filter for terminal DA1 of built-in option FR-
A7AZ.
{
—
—
866
*
Torque monitoring
reference
150%
0 to 400%
Set a full scale value when output torque monitor value is
output in analog.
{
—
—
867
AM output filter
0.01s
0 to 5s
Set the output filter of terminal AM.
{
{
—
A700
F700
E700
D700
* The above parameters allow its setting to be changed during operation in any operation mode even if [
Pr. 77 Parameter write
selection
= 0] (initial value) .
Summary of Contents for FR-A700 Series
Page 245: ...279 2 PARAMETER PARAMETER MEMO ...
Page 440: ...474 PARAMETER MEMO ...
Page 522: ...556 SELECTION MEMO ...