Monitor display and monitor output signals
Parameter
6 - 322
Monitor description list (Pr. 52)
●
Set the monitor to be displayed on the operation panel (FR-DU07) and parameter unit (FR-
PU04/FR-PU07) in Pr. 52 "DU/PUmain display data selection".
●
Set the monitor to be output to the terminal CA ((analog current output) in Pr. 54 "CA terminal
function selection".
●
Set the monitor to be output to the terminal AM (analog voltage output (0 to 10VDC voltage
output)) in Pr. 158 "AM terminal function selection".
Types of Monitor
Increments
Pr. 52
Pr. 54 (CA)
Pr. 158 (AM)
Setting
Full-scale
value of the
terminal CA
and AM
Description
DU LED
PU Main
Monitor
Output frequency
0.01Hz
0/100
1
Pr. 55
Displays the inverter output frequency.
Output current
0.01A/0.1A
0/100
2
Pr. 56
Displays the inverter output current
effective value.
Output voltage
0.1V
0/100
3
800V
Displays the inverter output voltage.
Alarm display
—
0/100
—
—
Displays 8 past alarms individually.
Frequency setting
0.01Hz
5
5
Pr. 55
Displays the set frequency.
Running speed
1r/min
6
6
The value
converted
with the
Pr. 37 value
from Pr. 55
Displays the motor speed. (depending
on Pr. 37 and Pr. 144 settings, refer to
page 6-318)
Motor torque
0.1%
7
7
Pr. 866
Display the motor torque in percent-
age on the assumption that the rated
motor torque is 100%
(0% is displayed during V/f control)
Converter output voltage
0.1V
8
8
800V
Displays the DC bus voltage value.
Regenerative brake duty
0.1%
9
9
Pr. 70
Brake duty set in Pr. 30 and Pr. 70.
Electronic thermal relay
function load factor
0.1%
10
10
100%
Displays the motor thermal cumulative
value on the assumption that the ther-
mal operation level is 100%.
Output current peak
value
0.01A/0.1A
11
11
Pr. 56
Retain the peak value of the output
current monitor and display (cleared at
every start).
Converter output voltage
peak value
0.1V
12
12
800V
Retain the peak value of the DC bus
voltage value (cleared at every start).
Input power
0.01kW/0.1kW
13
13
Rated
inverter
power × 2
Display power of the inverter input
side
Output power
0.01kW/0.1kW
14
14
Rated
inverter
power × 2
Display power of the inverter output
side
Load meter
0.1%
17
17
100%
Torque current is displayed in % on
the assumption that the Pr. 866 setting
is 100%
Motor excitation current
0.01A/0.1A
18
18
Pr. 56
Display the excitation current of the
motor
Position pulse
—
19
—
—
Display the number of pulses per rota-
tion of the motor when orientation con-
trol is valid
Tab. 6-92:
Monitor description list (1)
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......