Enclosure design
Installation
2 - 10
2.4.2 Inverter
placement
Clearances around the inverter
Always observe the specified minimum clearances to ensure good heat dissipation and ade-
quate accessibility of the frequency inverter for servicing.
Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed
above the inverter should be heat resistant.
I001005E
Fig. 2-8:
Clearances
NOTE
For replacing the cooling fan of the 04320 or more, 30cm of space is necessary in front of
the inverter. Refer to section 8.1.7 for fan replacement.
Ambient temperature and humidity
Clearances (side)
Clearances (front)
Leave enough clearances and take
cooling measures.
In
v
e
rt
er
Measurement
position
5cm
5cm
5cm
01800 or less
02160 or more
≥
10cm
≥
5cm
≥
5cm
≥
10cm
≥
20cm
≥
10cm
≥
10cm
≥
20cm
1cm or more for 00126 or less
≥
5cm
Measurement
position
In
v
e
rt
er
Temperature:
−
10–50°C (LD,
ND
, HD)
−
10–40°C (SLD)
Initial setting
Ambient humidity: 90% RH maximum