Basic settings
External operation
FR-A700 EC
5 - 55
I001091E
Fig. 5-32:
Operate the inverter by using the analog voltage input
NOTES
When you want to operate in the external operation mode always at powering on or when
you want to save the trouble of input, set "2" (external operation mode) in Pr. 79 "Operation
mode selection" to choose external operation mode always.
Pr. 178 "STF terminal function selection" must be set to "60" (or Pr. 179 "STR terminal func-
tion selection" must be set to "61"). (All are initial values.)
Power on
→
operation mode check
For the initial setting, the inverter operates in the
external operation mode "EXT" when powering
on. Check that the operation command indication
is "EXT". If not displayed, press the PU/EXT key
to change to the external "EXT" operation mode.
If the operation mode still does not change, set
Pr. 79 to "0" to change to the external operation
mode. (Refer to section 5.1.6.)
Turn the start signal STF or STR on. Operation
status indication FWD or REV flickers.
CAUTION:
When both the forward and reverse signal are
turned on, the inverter will not start. Also, if
both switches turn on while running, the
inverter stops.
Acceleration
→
constant speed
Turn the volume (frequency setting potentiometer)
clockwise slowly to full.
The frequency value on the indication increases
according to Pr. 7 "Acceleration time" until 50Hz
is displayed.
Deceleration
Turn the volume (frequency setting potentiometer)
counter clockwise slowly to full.
The frequency value of the indication decreases
according to Pr. 8 "Deceleration time" until 0.00Hz
is displayed.
The motor stops.
Stop
Turn the start switch STF or STR off.
Operation
Display
Stop
Forward
rotation
Reverse
rotation
ON
ON
Reverse
rotation
Forward
rotation
OFF
Flickering
Flickering
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......