13.6.7
Use example (utilization of clock data)
The clock data built in the F930GOT can be transferred to a data register in the PLC for later
utilization while a specified bit device is ON. The clock data built in the F930GOT is stored in
the following registers. However, only the GOTR-PACK can handle these registers.
GD0: Current time (second)
GD1: Current time (minute)
GD2: Current time (hour)
GD3: Current time (day)
GD4: Current time (month)
GD5: Current time (year)
GD6: Current time (day of week)
Example: When the clock data (year, month, day, hour, minute and second) is transferred to
the register D100 in the PLC at every 30 seconds while M10 is ON
Select "Observe Status" in the screen creation software.
1) Select "Project", and set the cycle to 30 seconds.
2) Set the trigger 1 to "M10, ON".
3) Select "Word Set (16-bit)" as the operation, and set the number of points to "7".
4) Set "Storing Device" to "D100", "Fixed" to "0" and "Indirect Device" to "GD0".
5) Set the transfer method to "BM0V".
When this data is transferred to the F930GOT, the current time is stored in D100 at every 30
seconds while M100 is ON.
Summary of Contents for F930GOT-BWD-E
Page 1: ...USER S MANUAL F930GOT BWD E ...
Page 4: ...Graphic Operation Terminal F930GOT ii ...
Page 6: ...Graphic Operation Terminal F930GOT iv ...
Page 14: ...vi ...
Page 60: ...Graphic Operation Terminal F930GOT Start up 2 2 10 MEMO ...
Page 68: ...Graphic Operation Terminal F930GOT Screen Mode 3 3 8 MEMO ...
Page 120: ...Graphic Operation Terminal F930GOT Creation of Display Screens 8 8 30 ...
Page 200: ...Graphic Operation Terminal F930GOT Changeover of Display Screen FX PCS DU WIN E 10 10 18 ...
Page 272: ...Graphic Operation Terminal F930GOT Additional Functions in V 2 00 or later 13 13 24 MEMO ...