Graphic Operation Terminal F930GOT
Introduction 1
1-13
1.8
Connection of MELSEC FX/A Series (CPU PORT)
Connect the GOT to the programming connector in the PLC, and perform communication.
This communication method is easy because sequence programs, setting and interface are
not required once the connected PLC is set in the operation environment setting (on the SET-
UP MODE screen).
Use the following cables in connection of the PLC.
1) Connection of the FX
1
/FX
2
/FX
2C
/A Series
2) Connection of the FX
0
/FX
0S
/FX
0N
/FX
2N
/FX
2NC
Series
* If the screen mode is selected while cables are not connected, a communication error occurs.
Table 1.3:
Series name
FX
0
/FX
0S
/FX
0N
/FX
2N
/FX
2NC
/FX/FX
2C
Series
CPU PORT (RS422)
(In 1:N connection, select "CPU PORT (RS232C)"
for the second and fourth GOTs.)
FX
2N
(when FX
2N
-232-BD is used)
CPU PORT (RS232C)
(In 1:N connection, select "CPU PORT (RS422)"
for the second and fourth GOTs.)
AnN, AnA, AnS, AnSJ, AnSH, A1SJH, A2C, A2CJ,
A0J2H, AnU, AnUS, A2USH, A1FXCPU
CPU PORT (RS422)
(In 1:N connection, select "CPU PORT (RS232C)"
for the second and fourth GOTs.)
Motion controller
A171SCPU-S3
A171SHCPU
A172SHCPU
A272UHCPU
CPU PORT (RS422)
(In 1:N connection, select "CPU PORT (RS232C)"
for the second and fourth GOTs.)
OU
T
I N
OU
T
CP
U¥E
PR
OG
¥E
5
4
3
2
1
0
7
6
5
4
3
2
1
0
X7
X6
X5
X4
X3
X2
X1
X0
CO
M
N
L
Y5
Y4
Y3
Y2
CO
M2
Y1
CO
M1
Y0
CO
M0
CO
M
24+
RU
N
PO
WE
R
➀
F930GOT
➁
FX-40DU-CAB (3 m),
FX-40DU-CAB-10M (10 m),
FX-40DU-CAB-20M (20 m) or
FX-40DU-CAB-30M (30 m)
➂
FX-50DU-CAB0 (3 m),
FX-50DU-CAB0-1M (1 m),
FX-50DU-CAB0-10M (10 m),
FX-50DU-CAB0-20M (20 m) or
FX-50DU-CAB0-30M (30 m)
➃
FX/FX
2C
Series PLC
➄
A Series PLC
AnN, AnA, AnS, AnSJ, AnSH, A1SJH, A2C,
A2CJ, A0J2H, AnU, AnUS, A2USH, A1FX, CPU
➅
FX
0
/FX
0S
/FX
0N
/FX
2N
/FX
2NC
Series PLC
➆
Motion controller
A171SCPU-S3, A171SHCPU, A172SHCPU,
A272UHCPU
1)
2)
Summary of Contents for F930GOT-BWD-E
Page 1: ...USER S MANUAL F930GOT BWD E ...
Page 4: ...Graphic Operation Terminal F930GOT ii ...
Page 6: ...Graphic Operation Terminal F930GOT iv ...
Page 14: ...vi ...
Page 60: ...Graphic Operation Terminal F930GOT Start up 2 2 10 MEMO ...
Page 68: ...Graphic Operation Terminal F930GOT Screen Mode 3 3 8 MEMO ...
Page 120: ...Graphic Operation Terminal F930GOT Creation of Display Screens 8 8 30 ...
Page 200: ...Graphic Operation Terminal F930GOT Changeover of Display Screen FX PCS DU WIN E 10 10 18 ...
Page 272: ...Graphic Operation Terminal F930GOT Additional Functions in V 2 00 or later 13 13 24 MEMO ...