60
Stand-alone option
Name (model)
Specification and Structure
Enclosure surface
operation panel
FR-PA07
An operation panel that enables inverter operation and monitoring of frequency setting, etc. from the enclosure surface.
Outline drawing and enclosure cut dimension drawing
(Refer to page 16)
(Note) 1. The operation panel cannot be removed from the inverter.
2. The separate parameter unit connection cable (FR-CB20
) is required.
DIN rail installation
attachment
FR-UDA
An attachment to install an FR-F700PJ series inverter to a DIN rail.
Outline dimension drawing
[FR-UDA01]
[FR-UDA02]
[FR-UDA03]
AC reactor (for power
supply coordination)
FR-HAL-(H)
K
Improves the power factor and reduces the harmonic current at the input side. Connect an AC reactor at the input side of the inverter.
Selection method
Select an AC reactor according to the applied motor capacity.
(When a general-purpose motor is used, select it according to the motor capacity even if the capacity is smaller than the inverter capacity.)
Connection diagram
Outline dimension
Specification
Item
Description
Surrounding air
temperature
-10°C to +50°C (non-freezing)
Ambient humidity
90%RH or less (non-condensing)
Storage
temperature
-20°C to +60°C
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum altitude/
Vibration
1,000m or less, 5.9m/s
2
or less
Power supply
Power input from the inverter
Connection method
Connection using the parameter unit connection cable (FR-CB20
)
Selection table
Installation attachment
model
Inverter capacity
FR-F720PJ
FR-F740PJ
FR-UDA01
0.4K, 0.75K
FR-UDA02
1.5K, 2.2K
0.4K to 3.7K
FR-UDA03
3.7K
108
67
68
67
128
128
4-M4 0.7 screw
8.7
3-M4 0.7 screw
Hook
Hook
15
15
10
8.7
8.7
128
67
170
4-M4 0.7 screw
Hook
14.4
(Unit: mm)
M
R/L1
S/L2
T/L3
U
V
W
R
S
T
X
Y
Z
Three-phase AC
power supply
Inverter
FR-HAL
Motor
(Unit mm)
(Note) 1. Approximately 88% of the power factor improving effect can be obtained (92.3% when calculated with 1
power factor for the fundamental wave according to the Architectural Standard Specifications (Electrical Installation) (2013 revision)
supervised by the Ministry of Land, Infrastructure, Transport and Tourism of Japan).
2. This is a sample outline dimension drawing. The shape differs by the model. W1 and D1 indicate distances between installation holes. The
installation hole size is indicated by d.
3. Install AC reactors (FR-HAL) on a horizontal or vertical surface.
4. Keep enough clearance around the reactor because it heats up. (Keep a clearance of minimum 10cm each on top and bottom and minimum
5cm each on right and left regardless of the installation orientation.)
Model
W W1
H
D
D1
d
Mass
(kg)
Model
W W1
H
D
D1
d
Mass
(kg)
20
0V
0.4K
104
84
99
72
40
M5
0.6
40
0V
H0.4K
135 120 115
64
45
M4
1.5
0.75K
104
84
99
74
44
M5
0.8
H0.75K
135 120 115
64
45
M4
1.5
1.5K
104
84
99
77
50
M5
1.1
H1.5K
135 120 115
64
45
M4
1.5
2.2K
115
40
115
77
57
M6
1.5
H2.2K
135 120 115
64
45
M4
1.5
3.7K
115
40
115
83
67
M6
2.2
H3.7K
135 120 115
74
57
M4
2.5
5.5K
115
40
115
83
67
M6
2.3
H5.5K
160 145 142
76
55
M4
3.5
7.5K
130
50
135 100
86
M6
4.2
H7.5K
160 145 142
96
75
M4
5.0
11K
160
75
164 111
92
M6
5.2
H11K
160 145 146
96
75
M4
6.0
15K
160
75
167 126 107
M6
7.0
H15K
220 200 195 105
70
M5
9.0
Less than D
D1
W
W1
H