Technical Data
Mitsubishi Electric, MA00777A
3-1
3
Technical Data
Parameter
E1071
Front panel, W x H x D 219 x 154 x 6 mm
Mounting depth
55 mm (155 mm including clearance)
Front panel seal
IP 66
Rear panel seal
IP 20
Keyboard material/
Front panel
Touch screen: Polyester on glass *, 1 million finger touch
operations.
Overlay: Autotex F250 *.
Reverse side material
Powder-coated aluminum
Weight
1.1 kg
Serial port RS422/
RS485
25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC.
Serial port RS232C
9-pin D-sub contact, male with standard locking screws 4-40
UNC.
Ethernet
Shielded RJ 45
USB
Host type A (USB 1.1), max output current 500mA
Device type B (USB 1.1)
CF-slot
Compact flash, type I and II
Flash memory for
application
12 MB (incl. fonts)
Real time clock
±20 PPM + error because of ambient temperature and supply
voltage.
Total max error: 1 min/month at 25
°
C
Minimum life of the real time clock battery: 3 years
Temperature coefficient: 0.004 ppm/
°
C
2
Power consumption at
rated voltage
Normal: 0.4 A
Maximum: 0.9 A
Display
TFT-LCD. 640 x 480 pixels, 64K color.
CCFL backlight lifetime at the ambient temperature of
+25
°
C: >50,000 h.
Active area of display,
W x H
131.5 x 98.6 mm
Fuse
Internal DC fuse, 3.15 AT, 5 x 20 mm
Power supply
+24V DC (20 - 30V DC). 3-pin jack connection block.
CE: The power supply must conform with the requirements
for SELV or PELV according to IEC 950 or IEC 742.
UL: The power supply must conform with the requirements
for class II power supplies.
Ambient temperature
Vertical installation: 0
°
to +50
°
C
Horizontal installation: 0
°
to +40
°
C
Storage temperature
-20
°
to +70
°
C
Relative humidity
5 - 85 % non-condensed
EMC tests on the
operator terminal
The operator terminal conforms with the essential protection
requirements in article 4 of the directive 89/336/EEC. Noise
tested according to EN610
0
0-6-4 emission and EN61000-6-2
immunity.
UL, cUL approvals
(when procuct or
packing is marked)
UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only
DNV
Yes
NEMA
4x indoor use only
* See section