2. EXTERNAL DIMENSIONS
WY-Series
PQHY-P288, 312, 336, 360TSLMU-A1
Unit: mm(in)
c
d
b
a
f
e
To
indoor unit
Liquid
T
winning pipe<optional parts>
Gas Twinning pipe<optional parts>
To indoor unit
Heat Source unit 2
Heat Source unit 1
CMY
-Y200CBK2
PQHY
-P144TLMU-A1
PQHY
-P312TSLMU-A1
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.T
winning pipes should not be tilted more than 15 degrees from the horizontal plane.
3.See the Installation Manual for the details of
T
w
inning pipe installation.
4.The pipe section before the
T
w
inning pipe (sections "a" and "b" in the figure) must have at least 500mm(19-1
1/16)
of straight section (*including the straight pipe that is supplied with the
T
w
inning pipe).
5.Only use the
T
w
inning pipe by Mitsubishi (optional parts).
b
a
Gas
Liquid
Heat Source unit 2
Heat Source unit 1
Indoor unit~T
winning pipe
Tw
inning Kit(optional parts)
Component unit name
Package unit name
T
w
inning pipe connection size
PQHY
-P288TSLMU-A1
PQHY
-P144TLMU-A1
PQHY
-P168TLMU-A1
PQHY
-P168TLMU-A1
PQHY
-P336TSLMU-A1
d
c
Gas
Liquid
Tw
inning pipe~Heat Source unit 1
f
e
Gas
Liquid
Tw
inning pipe~Heat Source unit 2
ø41.28(1-5/8)
PQHY
-P360TSLMU-A1
PQHY
-P144TLMU-A1
PQHY
-P192TLMU-A1
PQHY
-P168TLMU-A1
PQHY
-P168TLMU-A1
ø19.05(3/4)
ø12.7(1/2)
ø28.58(1-1/8)
ø15.88(5/8)
ø28.58(1-1/8)
ø12.7(1/2)
ø34.93(1-3/8)
ø15.88(5/8)
880(34-1
1
/16)
20(13/16)
880(34-1
1
/16)
550(21-1
1/16)
1450(57-1/8)
1780(70-1/8)