MEES19K187
PQ
RY-P-T
(S)L
MU-A
1, Y(S)L
M
U-A
1, Z(
S)LMU
-A1
360
1. Piping Design
1-4. Compatibility
GA1/HA1/GB1/HB1 type and JA1/KA1/KB1 type can be mixed.
The only combination that is not available is mix of GB1/HB1 type and KB1 type.
When mixing GA1/HA1/GB1/HB1 type and JA1/KA1/KB1 type, specifications and restrictions is according to
GA1/HA1/GB1/HB1type. (piping length, connectable number of Sub BC)
Outdoor/Heat source unit
BC controller
Compatibility
PQRY-P-T/Y(S)LMU, PQRY-P-Z(S)LMU
G1 type
Compatible
PURY-P-T/Y(S)LMU S/W Ver. 7.08 or later
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
J1 type
Compatible
Outdoor/Heat source unit
BC controller
Compatibility
Main
Sub
PQRY-P-T/Y(S)LMU S/W Ver. 6.42 or later
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
JA1/KA1 type
GB1/HB1 type GB1/HB1 type
Compatible
JA1/KA1 type
KB1 type
GB1/HB1 type
Not compatible
JA1/KA1 type
GB1/HB1 type
Compatible
GA1/HA1 type
KB1 type
KB1 type
Compatible
GA1/HA1 type
KB1 type
GB1/HB1 type
Not compatible
GA1/HA1 type
KB1 type
Compatible
Outdoor/Heat source unit
BC controller
Compatibility
Main
Sub
PQRY-P-T/Y(S)LMU S/W Ver. 6.42 or later
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
JA1/KA1 type
KB1 type
Compatible(*)
*Up to 11 Sub BC controllers can be connected (KB1 type only).