MEES19K187
PQH
Y
-P
-T
(S)L
MU-A1
, Y(S)L
M
U-A1
25
1. SPECIFICATIONS
WY-Series
Heat Source Model
PQHY-P216YLMU-A1 < For Ground source >
Indoor Model
Non-Ducted
Ducted
Power source
3-phase 3-wire 460 V ±10% 60 Hz
Cooling capacity
*1, 2 BTU/h
216,000
(Nominal)
kW
63.3
Power input
kW
19.23
(460) Current input
A
26.8
(Rated)
BTU/h
206,000
kW
60.4
Power input
kW
17.72
16.10
(460) Current input
A
24.7
22.4
Temp. range of
Indoor
W.B.
59~75°F (15~24°C)
cooling
Inlet water
ºF
23~113°F (-5~45°C)
Heating capacity
*3, 4 BTU/h
243,000
(Nominal)
kW
71.2
Power input
kW
13.04
(460) Current input
A
18.1
(Rated)
BTU/h
232,000
kW
68.0
Power input
kW
12.01
12.34
(460) Current input
A
16.7
17.2
Temp. range of
Indoor
D.B.
59~81°F (15~27°C)
heating
Inlet water
ºF
23~113°F (-5~45°C)
Indoor unit
Total capacity
50~130% of heatsource unit capacity
connectable
Model/Quantity
P04~P96/2~50
Sound pressure level (measured in anechoic room)
dB <A>
58.0
Refrigerant
Liquid pipe
in. (mm)
5/8 (15.88) Brazed
piping diameter
Gas pipe
in. (mm)
1-1/8 (28.58) Brazed
Minimum Circuit Ampacity
A
31
Maximum Overcurrent Protection
A
50
Circulating water
Water flow rate
G/h
3,044
G/min (gpm)
50.7
m
3
/h
11.52
L/min
192
cfm
6.8
Pressure drop
psi
6.53
kPa
45
Operating volume
G/h
1,585 ~ 3,804
range
G/min (gpm)
26.4 ~ 63.4
m
3
/h
6.0 ~ 14.4
Compressor
Type x Quantity
Inverter scroll hermetic compressor x 1
Starting method
Inverter
Motor output
kW
14.5
Case heater
kW
0.045 (240 V)
Lubricant
MEL32
External finish
Galvanized steel sheets
External dimension H x W x D
in.
57-1/8 x 34-11/16 x 21-11/16
mm
1,450 x 880 x 550
Protection
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
devices
Inverter circuit
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Refrigerant
Type x original charge
R410A x 25 lbs + 13 oz (11.7 kg)
Control
LEV and HIC circuit
Net weight
lbs (kg)
567 (257)
Heat exchanger
plate type
Water volume in plate
G
2.64
l
10.0
Water pressure Max.
psi
290
MPa
2.0
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe, tube-in-tube structure
Drawing
External
KL94C234
Wiring
KE94G419
Standard
Document
Installation Manual
attachment
Accessory
Details refer to External Drw
Optional parts
joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-Y202S-G2, CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation
Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
Add brine to circulating water when a unit is operating at water temperature below 50°F (10°C), and turn DipSW4 (773) ON before power ON.
It is recommended to set the brine concentration to a percentage that will keep the freezing temperature at -15°C or less.
Notes:
Unit converter
1.<Standard CITY MULTI indoor unit> Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C), Brine concentration 0%
2.<PWFY-P36/72NMU-E2-AU> Nominal cooling conditions
Inlet water Temp.: 86°F (30°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 73°F (23°C), Water flow rate: 1.93 m
3
/h (8.3 gpm) <P36>/3.86 m
3
/h (16.6 gpm) <P72>,
Brine concentration 0%
3.<Standard CITY MULTI indoor unit> Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B.(20°CD.B.), Inlet water temperature: 68°F (20°C), Brine concentration 0%
4.<PWFY-P36/72NMU-E2-AU> Nominal heating conditions
Inlet water Temp.: 68°F (20°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 86°F (30°C), Water flow rate: 2.15 m
3
/h (9.2 gpm) <P36>/4.30 m
3
/h (18.5 gpm) <P72>,
Brine concentration 0%
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
0000005752.BOOK 25 ページ 2020年2月28日 金曜日 午前10時8分